CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 4 Input Register 15
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentActual.Cor_AnalogInput6
R
30031
Universal inputs
The scaled and filtered value of UAI2
VentActual.Cor_AnalogInput7
R
30032
Universal inputs
The scaled and filtered value of UAI3
VentActual.Cor_AnalogInput8
R
30033
Universal inputs
The scaled and filtered value of UAI4
VentSettings.Cor_Ai1(0)
X
30034
Analogue inputs
Connected signal on AI1:
0=Not used
1=Outdoor temp
2=Supplytemp
3=Extracttemp
4=Roomtemp1
5=Roomtemp2
6=Exhausttemp
7=Extrasensor
8=SAF pressure
9=EAF pressure
10=Deicingtemp
11=Frost prot.temp
12=CO
2
13=Humidity room
14=Humidity duct
15=Extra unit temp
16=External SAF control
17=External EAF control
18=SAF pressure 2
19=Humidity outdoor
VentSettings.Cor_Ai2
X
30035
Analogue inputs
Connected signal on AI2:
VentSettings.Cor_Ai3
X
30036
Analogue inputs
Connected signal on AI3:
VentSettings.Cor_Ai4
X
30037
Analogue inputs
Connected signal on AI4:
VentSettings.Cor_UAi1
X
30038
Universal inputs
Connected signal on UAI1:
0=Not used
1=Outdoor temp
2=Supplytemp
3=Extracttemp
4=Roomtemp1
5=Roomtemp2
6=Exhausttemp
7=Extrasensor
8=SAF pressure
9=EAF pressure
10=Deicingtemp
11=Frost prot.temp
12=CO
2
13=Humidity room
14=Humidity duct
15=Extra unit temp
16=External SAF control
17=External EAF control
18=SAF pressure 2
19=Humidity outdoor
VentSettings.Cor_UAi2
X
30039
Universal inputs
Connected signal on UAI2: (See
signal list for UAI1)