CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 4 Input Register 17
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_UDi1
X
30050
Universal inputs
Connected signal on UDI1:
0=Not used
1=SAF-Ind
2=EAF-Ind
3=P1-Heating
4=P1-Exchanger
5=P1-Cooling
6=Filter guard
7=Fire alarm
8=Fire damper-ind
9=Ext run 1/1
10=Ext run ½
11=External alarm
12=External switch
13=Flow guard
14=Rot.sent.exch
15=De-icing
16=Frostprotection
17=Overheatprotection
18=Recirculation run
19=Change over
20=Filter guard 2
VentSettings.Cor_UDi2
X
30051
Universal inputs
Connected signal on UDI2: (See
signal list for UDI1)
VentSettings.Cor_UDi3
X
30052
Universal inputs
Connected signal on UDI3: (See
signal list for UDI1)
VentSettings.Cor_UDi4
X
30053
Universal inputs
Connected signal on UDI4: (See
signal list for UDI1)
QAnaOut.AQ1
R
30054
Analogue
outputs
Value of AO1
QAnaOut.AQ2
R
30055
Analogue
outputs
Value of AO2
QAnaOut.AQ3
R
30056
Analogue
outputs
Value of AO3
QAnaOut.AQ4
R
30057
Analogue
outputs
Value of AO4
QAnaOut.AQ5
R
30058
Analogue
outputs
Value of AO5
VentSettings.Cor_Ao1(0)
X
30059
Analogue
outputs
Connected signal on AO1:
0=Not used
1=Y1-Heating
2=Y2-Exchanger
3=Y3-Cooling
4=SAF
5=EAF
6=Y6-Humidity
7=Split of Y1, Y2 or Y3
8=Extra unit
9=Heat/Cool (change over)
10=Extra sequence Y4