CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

20 Chapter 4 Input Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
AlaData.AlaPt26_Status
X
30096
Alarm Status
Low efficiency
AlaData.AlaPt27_Status
X
30097
Alarm Status
Sensor error outdoor temp
AlaData.AlaPt28_Status
X
30098
Alarm Status
Analogue deicing
AlaData.AlaPt29_Status
X
30099
Alarm Status
Rotation guard exchanger
AlaData.AlaPt30_Status
X
30100
Alarm Status
Fire damper malfunction
AlaData.AlaPt31_Status
X
30101
Alarm Status
Supply air fan control error
AlaData.AlaPt32_Status
X
30102
Alarm Status
Extract air fan control error
AlaData.AlaPt33_Status
X
30103
Alarm Status
Supply air fan external operation
AlaData.AlaPt34_Status
X
30104
Alarm Status
Extract air fan external operation
AlaData.AlaPt35_Status
X
30105
Alarm Status
Ventilation manual mode
AlaData.AlaPt36_Status
X
30106
Alarm Status
Manual supply air control
AlaData.AlaPt37_Status
X
30107
Alarm Status
Supply air fan manual mode
AlaData.AlaPt38_Status
X
30108
Alarm Status
Manual supply air fan freq. control
AlaData.AlaPt39_Status
X
30109
Alarm Status
Extract air fan manual mode
AlaData.AlaPt40_Status
X
30110
Alarm Status
Manual extract air fan freq. control
AlaData.AlaPt41_Status
X
30111
Alarm Status
Manual heater control
AlaData.AlaPt42_Status
X
30112
Alarm Status
Manual exchanger control
AlaData.AlaPt43_Status
X
30113
Alarm Status
Manual cooler control
AlaData.AlaPt44_Status
X
30114
Alarm Status
Manual P1 heater
AlaData.AlaPt45_Status
X
30115
Alarm Status
Manual P1 exchanger
AlaData.AlaPt46_Status
X
30116
Alarm Status
Manual P1 cooler
AlaData.AlaPt47_Status
X
30117
Alarm Status
Manual fire damper
AlaData.AlaPt48_Status
X
30118
Alarm Status
Internal battery error
VentActual.Cor_HeatCV1(0)
R
30119
Analogue
outputs
Control signal heating Y1 (0...10 V)
VentActual.Cor_ExchCV1
R
30120
Analogue
outputs
Control signal exchanger Y2 (0...10
V)
VentActual.Cor_CoolCV1
R
30121
Analogue
outputs
Control signal cooler Y3 (0...10 V)
VentActual.Cor_SAF
R
30122
SAF/EAF
Pressure and
Flow
Control signal supply air fan (0...10
V)
VentActual.Cor_EAF
R
30123
SAF/EAF
Pressure and
Flow
Control signal extract air fan (0...10
V)
VentActual.Cor_Humidity
R
30124
Humidity
Control signal humidity (0...10 V)
VentActual.Cor_Split
R
30125
Analogue
outputs
Control signal split (0...10 V)