CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 4 Input Register 21
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentActual.Cor_SupplyPID_Output
R
30126
Supply, Extract
and Room
temperatures
Supply controller output (0...100 %)
VentActual.Cor_ExhaustPID_Output
R
30127
Supply, Extract
and Room
temperatures
Extract controller output (0...100 %)
VentActual.Cor_SAFPID_Output
R
30128
SAF/EAF
Pressure and
Flow
SAF controller output (0...100 %)
VentActual.Cor_EAFPID_Output
R
30129
SAF/EAF
Pressure and
Flow
EAF controller output (0...100 %)
VentActual.Cor_FrostPID_Output
R
30130
Frost protection
Frost protection controller output if
ventilation unit is stopped (0...100 %)
VentActual.Cor_CO2PID_Output
R
30131
CO
2
CO
2
controller output (0...100 %)
VentActual.Cor_RoomPID_Output
R
30132
Supply, Extract
and Room
temperatures
Room controller output (0...100 %)
VentActual.Cor_DeIcePID_Output
R
30133
Extract air temp/
De-icing
exchanger
De-icing controller output (0...100 %)
VentActual.Cor_HumidityPID_Output
R
30134
Humidity
Humidity controller output (0...100
%)
VentActual.Cor_RoomTemp
R
30135
Supply, Extract
and Room
temperatures
Room temperature 1 and 2
AlaData.AlaPt49_Status
X
30137
Alarm Status
Sensor error, supply air temp.
AlaData.AlaPt50_Status
X
30138
Alarm Status
Sensor error, extract air temp.
AlaData.AlaPt51_Status
X
30139
Alarm Status
Sensor error, room temp. 1
AlaData.AlaPt52_Status
X
30140
Alarm Status
Sensor error, room temp. 2
AlaData.AlaPt53_Status
X
30141
Alarm Status
Sensor error, extract air temp.
AlaData.AlaPt54_Status
X
30142
Alarm Status
Sensor error, extra sensor
AlaData.AlaPt55_Status
X
30143
Alarm Status
Sensor error SAF pressure
AlaData.AlaPt56_Status
X
30144
Alarm Status
Sensor error EAF pressure
AlaData.AlaPt57_Status
X
30145
Alarm Status
Sensor error, deicing temp.
AlaData.AlaPt58_Status
X
30146
Alarm Status
Sensor error, frost protection temp.
AlaData.AlaPt59_Status
X
30147
Alarm Status
Sensor error CO
2
AlaData.AlaPt60_Status
X
30148
Alarm Status
Sensor error Humidity room
AlaData.AlaPt61_Status
X
30149
Alarm Status
Sensor error Humidity duct
VentActual.Cor_ExtraUnitTemp(0)
R
30150
Extra Unit
Extra Unit temp