CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

24 Chapter 4 Input Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_ExpAi(0)
X
30198
Analogue inputs
Connected signal on AI1 Exp. Unit 1:
0=Not used
1=Outdoor temp
2=Supplytemp
3=Extracttemp
4=Roomtemp1
5=Roomtemp2
6=Exhausttemp
7=Extrasensor
8=SAF pressure
9=EAF pressure
10=Deicingtemp
11=Frost prot.temp
12=CO
2
13=Humidity room
14=Humidity duct
15=Extra unit temp
16=External SAF control
17=External EAF control
18=SAF pressure 2
19=Humidity outdoor
VentSettings.Cor_ExpAi(1)
X
30199
Analogue inputs
Connected signal on AI2 Exp. Unit 1
VentSettings.Cor_ExpAi(2)
X
30200
Analogue inputs
Connected signal on AI3 Exp. Unit 1
VentSettings.Cor_ExpAi(3)
X
30201
Analogue inputs
Connected signal on AI4 Exp. Unit 1
VentSettings.Cor_ExpAi(4)
X
30202
Analogue inputs
Connected signal on UAI1 Exp. Unit
1
VentSettings.Cor_ExpAi(5)
X
30203
Analogue inputs
Connected signal on UAI2 Exp. Unit
1
VentSettings.Cor_ExpAi(6)
X
30204
Analogue inputs
Connected signal on UAI3 Exp. Unit
1
VentSettings.Cor_ExpAi(7)
X
30205
Analogue inputs
Connected signal on UAI4 Exp. Unit
1
VentSettings.Cor_ExpAi(8)
X
30206
Analogue inputs
Connected signal on AI1 Exp. Unit 2
VentSettings.Cor_ExpAi(9)
X
30207
Analogue inputs
Connected signal on AI2 Exp. Unit 2
VentSettings.Cor_ExpAi(10)
X
30208
Analogue inputs
Connected signal on AI3 Exp. Unit 2
VentSettings.Cor_ExpAi(11)
X
30209
Analogue inputs
Connected signal on AI4 Exp. Unit 2
VentSettings.Cor_ExpAi(12)
X
30210
Analogue inputs
Connected signal on UAI1 Exp. Unit
2
VentSettings.Cor_ExpAi(13)
X
30211
Analogue inputs
Connected signal on UAI2 Exp. Unit
2
VentSettings.Cor_ExpAi(14)
X
30212
Analogue inputs
Connected signal on UAI3 Exp. Unit
2
VentSettings.Cor_ExpAi(15)
X
30213
Analogue inputs
Connected signal on UAI4 Exp. Unit
2