CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

28 Chapter 4 Input Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_ExpDo(0)
X
30258
Digital outputs
Connected signal on DO1 Exp. Unit
1:
0 = Not Used
1 = SAFStart1
2 = EAFStart1
3 = SAFStart2
4 = EAFStart2
5 = HeatingPumpStart
6 = ExchangerStart
7 = CoolingPumpStart
8 = FireDamper
9 = SumAlarm
10 = SumAlarmA
11 = SumAlarmB
12 = SAFFrequencyStart
13 = EAFFrequencyStart
14 = HeatingActivate
15 = ExchangerActivate
16 = CoolingActivate
17 = RecycleAirDamper
18 = FreshAirDamper
19 = ExtractAirDamper
20 = HeatingIncrease
21 = HeatingDecrease
22 = ExchangerIncrease
23 = ExchangerDecrease
24 = CoolingIncrease
25 = CoolingDecrease
26 = HeatStep1
27 = HeatStep2
28 = HeatStep3
29 = HeatStep4
30 = CoolStep1
31 = CoolStep2
32 = CoolStep3
33 = TimeChannel1
34 = TimeChannel2
35 = TimeChannel3
36 = TimeChannel4
37 = TimeChannel5
38 = Humidity start
39 = Extra unit start
40 = Heat/Cool step 1
41 = Heat/Cool step 2
42 = Heat/Cool step 3
43 = Night cool run
VentSettings.Cor_ExpDo(1)
X
30259
Digital outputs
Connected signal on DO2 Exp. Unit
1:
(See signal list for DO1)
VentSettings.Cor_ExpDo(2)
X
30260
Digital outputs
Connected signal on DO3 Exp. Unit
1:
(See signal list for DO1)