CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

30 Chapter 4 Input Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentActual.Cor_EAFMotorSpeedHz
R
30276
SAF/EAF
Pressure and
Flow
EAF Motor speed Hz
VentActual.Cor_EAFMotorCurrent
R
30277
SAF/EAF
Pressure and
Flow
EAF Motor current A
VentActual.Cor_EAFMotorPower
R
30278
SAF/EAF
Pressure and
Flow
EAF Motor Power % of nominal
VentActual.Cor_EAFAccumPower
R
30279
SAF/EAF
Pressure and
Flow
EAF Accumulated Power consuption
VentActual.Cor_ExtraUnitCV1(0)
R
30280
Extra Unit
Control signal Extra Unit
(0...10 V)
VentActual.Cor_ExtraUnitPID1_Outpu
t(0)
R
30281
Extra Unit
Extra Unit controller output (0...100
%)
VentActual.Cor_HeatCoolCV1
R
30282
Analogue
outputs
Control signal Heating or Cooling
controlled by changeover
(0...10 V)
VentActual.Cor_ExtraSeqCV1
R
30283
Analogue
outputs
Control signal extra sequence Y4
(0...10 V)
VentActual.Cor_UnitRunMode
X
30284
Actual/Setpoint
Unit run mode:
Modbus:
0=Off
1=Reduced speed
2=Normal speed
3=Stop because of alarm
BACnet:
1=Off
2=Reduced speed
3=Normal speed
4=Stop because of alarm
AlaData.AlaPt88_Status
X
30285
Alarm Status
Restart blocked after power-on
VentActual.Cor_IntakeAirTemp
R
30286
Actual/Setpoint
Intake air temperature
VentActual.Cor_ExtraSensor2
R
30287
Actual/Setpoint
Extrasensor 2 temperature
VentActual.Cor_ExtraSensor3
R
30288
Actual/Setpoint
Extrasensor 3 temperature
VentActual.Cor_ExtraSensor4
R
30289
Actual/Setpoint
Extrasensor 4 temperature
VentActual.Cor_ExtraSensor5
R
30290
Actual/Setpoint
Extrasensor 5 temperature
VentActual.Cor_ExtraSAFPressure
R
30291
SAF/EAF
Pressure and
Flow
Extrasensor SAF Pressure
VentActual.Cor_ExtraEAFPressure
R
30292
SAF/EAF
Pressure and
Flow
Extrasensor EAF Pressure