CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

34 Chapter 5 Holding Register
Chapter 5 Holding Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_Supply
Setpoint
R
40001
18°C
Supply, Extract and
Room temperatures
Setpoint supply air temperature when
constant supply air temperature
function
VentSettings.Cor_Curve1
_X1
R
40002
-20°C
Supply, Extract and
Room temperatures
Outdoor temp for first curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_X2
R
40003
-15°C
Supply, Extract and
Room temperatures
Outdoor temp for second curve point
for outdoor compensated setpoint
VentSettings.Cor_Curve1
_X3
R
40004
-10°C
Supply, Extract and
Room temperatures
Outdoor temp for third curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_X4
R
40005
-5°C
Supply, Extract and
Room temperatures
Outdoor temp for fourth curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_X5
R
40006
0°C
Supply, Extract and
Room temperatures
Outdoor temp for fifth curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_X6
R
40007
5°C
Supply, Extract and
Room temperatures
Outdoor temp for sixth curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_X7
R
40008
10°C
Supply, Extract and
Room temperatures
Outdoor temp for seventh curve point
for outdoor compensated setpoint
VentSettings.Cor_Curve1
_X8
R
40009
15°C
Supply, Extract and
Room temperatures
Outdoor temp for eighth curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_Y1
R
40010
25°C
Supply, Extract and
Room temperatures
Setpoint for first curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_Y2
R
40011
24°C
Supply, Extract and
Room temperatures
Setpoint for second curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_Y3
R
40012
23°C
Supply, Extract and
Room temperatures
Setpoint for third curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_Y4
R
40013
23°C
Supply, Extract and
Room temperatures
Setpoint for fourth curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_Y5
R
40014
22°C
Supply, Extract and
Room temperatures
Setpoint for fifth curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_Y6
R
40015
20°C
Supply, Extract and
Room temperatures
Setpoint for sixth curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_Y7
R
40016
18°C
Supply, Extract and
Room temperatures
Setpoint for seventh curve point for
outdoor compensated setpoint
VentSettings.Cor_Curve1
_Y8
R
40017
18°C
Supply, Extract and
Room temperatures
Setpoint for eight curve point for
outdoor compensated setpoint
VentSettings.Cor_Exhaus
tSetpoint
R
40018
21°C
Supply, Extract and
Room temperatures
Setpoint extract air temp if extract air
temp control function