CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 5 Holding Register 35
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_RoomS
etP
R
40019
21°C
Supply, Extract and
Room temperatures
Room setpoint if room temp control
function
VentSettings.Cor_NeedH
eatStart
R
40020
15°C
Supply, Extract and
Room temperatures
Room temp for start the unit if
intermittent heating control is active
VentSettings.Cor_NeedH
eatStop
R
40021
21°C
Supply, Extract and
Room temperatures
Room temp for stop the unit if
intermittent heating control is active
VentSettings.Cor_NeedC
oolStart
R
40022
30°C
Supply, Extract and
Room temperatures
Room temp for start the unit if
intermittent cooling control is active
VentSettings.Cor_NeedC
oolStop
R
40023
28°C
Supply, Extract and
Room temperatures
Room temp for stop the unit if
intermittent cooling control is active
VentSettings.Cor_SAFFu
llspeedPressure
R
40024
500 Pa
SAF/EAF Pressure
and Flow
Setpoint full speed supply air fan
pressure
VentSettings.Cor_SAFHa
lfspeedPressure
R
40025
250 Pa
SAF/EAF Pressure
and Flow
Setpoint reduced speed supply air fan
pressure
VentSettings.Cor_EAFFu
llspeedPressure
R
40026
500 Pa
SAF/EAF Pressure
and Flow
Setpoint full speed extract air fan
pressure
VentSettings.Cor_EAFHa
lfspeedPressure
R
40027
250 Pa
SAF/EAF Pressure
and Flow
Setpoint reduced speed extract air fan
pressure
VentSettings.Cor_SAFFu
llspeedAirFlow
R
40028
2000
m
3
/h
SAF/EAF Pressure
and Flow
Setpoint full speed supply air fan flow.
Scale factor = 1
VentSettings.Cor_SAFHa
lfspeedAirFlow
R
40029
1000
m
3
/h
SAF/EAF Pressure
and Flow
Setpoint reduced speed supply air fan
flow. Scale factor = 1
VentSettings.Cor_EAFFu
llspeedAirFlow
R
40030
2000
m
3
/h
SAF/EAF Pressure
and Flow
Setpoint full speed extract air fan flow.
Scale factor = 1
VentSettings.Cor_EAFHa
lfspeedAirFlow
R
40031
1000
m3/h
SAF/EAF Pressure
and Flow
Setpoint reduced speed extract air fan
flow. Scale factor = 1
VentSettings.Cor_CO2Se
tpoint
R
40032
1000
ppm
CO
2
Setpoint CO
2
VentSettings.Cor_FrostPr
otSPStop
R
40033
25°C
Frost protection
Setpoint frost protection if the
ventilation unit is stopped
VentSettings.Cor_FrostPr
otPGain
R
40034
5°C
Frost protection
P-Gain frost protection when running
(alarm limit+PGain)
VentSettings.Cor_DeIcin
gSetpoint
R
40035
-3°C
Extract air temp/De-
icing exchanger
Setpoint de-icing temp
VentSettings.Cor_DeIcin
gHyst
R
40036
1°C
Extract air temp/De-
icing exchanger
Hysteresis for stop of de-icing
VentSettings.Cor_Humidi
tySetpoint
R
40037
50 % RH
Humidity
Setpoint humidity room
VentSettings.Cor_Humidi
tyMaxDuct
R
40038
80 % RH
Humidity
Max limit humidity duct
VentSettings.Cor_Humidi
tyHyst
R
40039
20 % RH
Humidity
Hysteresis to start humidity control
after stop max limitation