CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 5 Holding Register 45
Signal name
EXOL type
Modbus address
Default value
Function
Description
TimeHp.Posts(23).From
Date
R
40310
01.01
Holidays
Start date holiday period 24 (MM.DD)
TimeHp.Posts(23).ToDat
e
R
40311
01.01
Holidays
End date holiday period 24 (MM.DD)
VentSettings.Cor_Supply
PID_PGain
R
40312
33°C
Settings, Control
Temp
P-band supply air control
VentSettings.Cor_Supply
PID_ITime
R
40313
100 s
Settings, Control
Temp
I-time supply air control
VentSettings.Cor_Exhaus
tPID_PGain
R
40314
100°C
Settings, Control
Temp
P-band extract air control
VentSettings.Cor_Exhaus
tPID_ITime
R
40315
300 s
Settings, Control
Temp
I-time extract air control
VentSettings.Cor_RoomP
ID_PGain
R
40316
100°C
Settings, Control
Temp
P-band room air control
VentSettings.Cor_RoomP
ID_ITime
R
40317
300 s
Settings, Control
Temp
I-time room air control
VentSettings.Cor_FrostPI
D_PGain
R
40318
100°C
Settings, Control
Temp
P-band switchdown mode
VentSettings.Cor_FrostPI
D_ITime
R
40319
100 s
Settings, Control
Temp
I-time switchdown mode
VentSettings.Cor_DeIceP
ID_PGain
R
40320
100°C
Settings, Control
Temp
P-band de-icing
VentSettings.Cor_DeIceP
ID_ITime
R
40321
100 s
Settings, Control
Temp
I-time de-icing
VentSettings.Cor_SAFPI
D_PGain
R
40322
500 Pa
Settings, Control
Pressure
P-band pressure control SAF
VentSettings.Cor_SAFPI
D_ITime
R
40323
60 s
Settings, Control
Pressure
I-time pressure control SAF
VentSettings.Cor_EAFPI
D_PGain
R
40324
500 Pa
Settings, Control
Pressure
P-band pressure control EAF
VentSettings.Cor_EAFPI
D_ITime
R
40325
60 s
Settings, Control
Pressure
I-time pressure control EAF
VentSettings.Cor_SAFAi
rFlowPID_PGain
R
40326
1000
m
3
/h
Settings, Control
Flow
P-band flow control SAF
VentSettings.Cor_SAFPI
D_ITime
R
40327
60 s
Settings, Control
Flow
I-time flow control SAF
VentSettings.Cor_EAFAi
rFlowPID_PGain
R
40328
1000
m
3
/h
Settings, Control
Flow
P-band flow control EAF
VentSettings.Cor_EAFPI
D_ITime
R
40329
60 s
Settings, Control
Flow
I-time flow control EAF
VentSettings.Cor_Humidi
tyPID_PGain
R
40330
100 %
RH
Settings, Control
Humidity
P-band humidity control