CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 5 Holding Register 47
Signal name
EXOL type
Modbus address
Default value
Function
Description
AlaData.AlaPt32_DelayV
alue
I
40352
30 min
Settings, Alarm
Delays
Alarm delay max control deviation
pressure EAF
AlaData.AlaPt26_DelayV
alue
I
40353
30 min
Settings, Alarm
Delays
Alarm delay low efficiency
AlaData.AlaPt1_DelayVa
lue
I
40354
120 s
Settings, Alarm
Delays
Alarm delay malfunction SAF
AlaData.AlaPt2_DelayVa
lue
I
40355
120 s
Settings, Alarm
Delays
Alarm delay malfunction EAF
AlaData.AlaPt3_DelayVa
lue
I
40356
5 s
Settings, Alarm
Delays
Alarm delay malfunction P1-Heating
AlaData.AlaPt4_DelayVa
lue
I
40357
5 s
Settings, Alarm
Delays
Alarm delay malfunction P1-Cooling
AlaData.AlaPt5_DelayVa
lue
I
40358
20 s
Settings, Alarm
Delays
Alarm delay malfunction P1-Exchanger
AlaData.AlaPt6_DelayVa
lue
I
40359
180 s
Settings, Alarm
Delays
Alarm delay filter monitoring
AlaData.AlaPt7_DelayVa
lue
I
40360
5 s
Settings, Alarm
Delays
Alarm delay flow switch
AlaData.AlaPt8_DelayVa
lue
I
40361
0 s
Settings, Alarm
Delays
Alarm delay frost protection
AlaData.AlaPt9_DelayVa
lue
I
40362
0 s
Settings, Alarm
Delays
Alarm delay frost protection
digital input
AlaData.AlaPt10_DelayV
alue
I
40363
0 s
Settings, Alarm
Delays
Alarm delay fire alarm
AlaData.AlaPt12_DelayV
alue
I
40364
0 s
Settings, Alarm
Delays
Alarm delay external alarm
AlaData.AlaPt23_DelayV
alue
I
40365
0 s
Settings, Alarm
Delays
Alarm delay electric heater
AlaData.AlaPt27_DelayV
alue
I
40366
5 s
Settings, Alarm
Delays
Alarm delay sensor error
AlaData.AlaPt29_DelayV
alue
I
40367
20 s
Settings, Alarm
Delays
Alarm delay rotation guard exchanger
VentSettings.Cor_AirUni
tAutoMode
X
40368
3
Manual/Auto
Running mode air unit:
Modbus:
0=Manual off
1=Manual reduced speed
2=Manual normal speed
3=Auto
BACnet:
1=Manual off
2=Manual reduced speed
3=Manual normal speed
4=Auto