CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 5 Holding Register 49
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_CoolC
oilManual
R
40382
0
Manual/Auto
Cooling controller output if manual
mode
VentSettings.Cor_Humidi
tyPID_Select
X
40383
2
Manual/Auto
Running mode
Humidification/Dehumidification:
0=Off
1=Manual
2=Auto
VentSettings.Cor_Humidi
tyPID_ManSet
R
40384
0
Manual/Auto
Humidification/Dehumidification
controller output if manual mode
VentSettings.Cor_HeatPu
mpAutoMode(0)
X
40385
2
Manual/Auto
Running mode P1-Heating:
0=Manual off
1=Manual on
2=Auto
VentSettings.Cor_ExchP
umpAutoMode
X
40386
2
Manual/Auto
Running mode P1-Exchanger:
0=Manual off
1=Manual on
2=Auto
VentSettings.Cor_CoolPu
mpAutoMode
X
40387
2
Manual/Auto
Running mode P1-Cooling:
0=Manual off
1=Manual on
2=Auto
VentSettings.Cor_FireDa
mperAutoMode
X
40388
2
Manual/Auto
Running mode fire damper:
0=Close
1=Open
2=Auto
VentSettings.Cor_FreshAir
DamperAutoMode
X
40389
2
Manual/Auto
Running mode fresh air damper:
0=Close
1=Open
2=Auto
VentSettings.Cor_Recycle
AirDamperAutoMode
X
40390
2
Manual/Auto
Running mode recirculation damper:
0=Close
1=Open
2=Auto
VentSettings.Cor_ExtractA
irDamperAutoMode
X
40391
2
Manual/Auto
Running mode extract air damper:
0=Close
1=Open
2=Auto
VentActual.Cor_Outdoor
temp(0)
R
40392
Actual/Setpoint
Outdoor temperature (Can be modified
if it’s not connected to a physical
analogue input).