CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 5 Holding Register 51
Signal name
EXOL type
Modbus address
Default value
Function
Description
TimePro.TimeGroupStatu
sCor_ExtraTimeGroup5
X
40399
4
Manual/Auto
Manual/Auto Timer output 5:
Modbus:
0=Manual-Off
1=Manual-On
2=Forced Off
3=Forced On
4=Auto
BACnet:
1=Manual-Off
2=Manual-On
3=Forced Off
4=Forced On
5=Auto
Alarms.AlaAcknow
X
40400
255
Alarm
Acknowledging,
Blocking and
Unblocking
External alarm acknowledge by setting
this signal to the alarm number that
should be acknowledge.
Alarms.AlaBlock
X
40401
255
Alarm
Acknowledging,
Blocking and
Unblocking
External alarm blocking by setting this
signal to the alarm number that should
be blocked.
Alarms.AlaUnBlock
X
40402
255
Alarm
Acknowledging,
Blocking and
Unblocking
External alarm unblocking by setting
this signal to the alarm number that
should be unblocked.
VentSettings.Cor_HeatPu
mpLimit
R
40403
10°C
Actual/Setpoint
If lower outdoor temp the heating pump
is not stopped
VentSettings.Cor_Supply
SetpointMax
R
40404
30°C
Supply, Extract and
Room temperatures
Max limit of supply setpoint when
cascade control
VentSettings.Cor_Supply
SetpointMin
R
40405
12°C
Supply, Extract and
Room temperatures
Min limit of supply setpoint when
cascade control
QSystem.Sec
X
40406
Real Time Clock
Real time clock: Second 0-59
QSystem.Minute
X
40407
Real Time Clock
Real time clock: Minute 0-59
QSystem.Hour
X
40408
Real Time Clock
Real time clock: Hour 0-23
QSystem.WDay
X
40409
Real Time Clock
Real time clock: Day of Week 1-7,
1=Monday
QSystem.Week
X
40410
Real Time Clock
Real time clock: Week number 1-53
QSystem.Date
X
40411
Real Time Clock
Real time clock: Day of month 1-31
QSystem.Month
X
40412
Real Time Clock
Real time clock: Month 1-12
QSystem.Year
X
40413
Real Time Clock
Real time clock: Year 0-99
VentSettings.Cor_Comp1
Pressure
R
40414
0
SAF/EAF Pressure
and Flow
Pressure compensation at breakpoint 1
VentSettings.
Cor_Comp1Temp
R
40415
-20
SAF/EAF Pressure
and Flow
Outdoor temp breakpoint 1 (must be
lower than breakpoint 2 temp)