CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

54 Chapter 5 Holding Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_Extern
alControl
X
40451
2
Manual/Auto
External control:
Modbus:
0=Extended run full speed
1=External stop
2=No external control
3=External stop with support control
BACnet:
1=Extended run full speed
2=External stop
3=No external control
4=External stop with support control
VentSettings.Cor_PreHea
tStart
R
40452
8
Settings,
PreTreatment
If outdoor temp. is lower, preheat is
activated
VentSettings.Cor_PreCoo
lStart
R
40453
19
Settings,
PreTreatment
If outdoor temp. is higher, precool is
activated
VentSettings.Cor_PreTre
atHyst
R
40454
1
Settings,
PreTreatment
Hysteresis to start/stop pretreatment
VentSettings.Cor_PreTre
atMinDiff
R
40455
1
Settings,
PreTreatment
Min. diff. intake air temp. and outdoor
air temp.
VentSettings.Cor_PreTre
atmentAutoMode
X
40456
2
Settings,
PreTreatment
Run mode pretreatment:
0=Closed
1=Open
2=Auto
VentSettings.Cor_PreTre
atFreeCool
X
40457
0
Settings,
PreTreatment
Select whether pretreatment should be
activated during free cooling
VentSettings.Cor_PreTre
atBlockTime
X
40458
6
Settings,
PreTreatment
Hour that pretreatment is blocked if
diff. intake/outdoor is too low
VentSettings.Cor_PreTre
atMinRunTime
X
40459
5
Settings,
PreTreatment
Min. runtime (minutes) for
pretreatment
VentSettings.Cor_Restart
PowerOn
X
40460
1
Settings, General
Automatic restart after power-up (=1)
VentSettings.Cor_DXFull
Speed
X
40461
0
Settings, General
Switch to full speed if DX-Cooling
VentSettings.Cor_Recycl
eSetPOffset
R
40462
0
Recirculation
Offset for recirculation setpoint
VentSettings.Cor_Recycl
eSetPControl
X
40463
0
Recirculation
Select if constant setpoint or setpoint
adjustment when recirculation runs:
0=Constant setpoint
1=Supply air setpoint with adjustment
VentSettings.Cor_Recycl
eTempControl
X
40464
0
Recirculation
Enable supply air temp control when
recirculation runs:
0=No temp control
1=Heating/cooling
2=Only heating
3=Only cooling
VentSettings.Cor_Deman
dCO2Value1
R
40465
800
CO
2
Activation of demand-controlled
ventilation, 1/2-speed