CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 5 Holding Register 57
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_NightC
oolSAFOutput
R
40486
0
Settings, Free cooling
SAF output when free cooling and
frequency fan: 0=The output is normal
speed
VentSettings.Cor_NightC
oolEAFOutput
R
40487
0
Settings, free cooling
EAF output when free cooling and
frequency fan: 0=The output is normal
speed
AlaData.AlaPt90_DelayV
alue
I
40488
180
Settings, Alarm
Delays
Filter guard 2
VentSettings.Cor_ExtraS
ensor1HighLimit(0)
R
40489
30
Settings, Alarm limits
Alarm limit high temp Extra sensor 1
VentSettings.Cor_ExtraS
ensor2HighLimit
R
40490
30
Settings, Alarm limits
Alarm limit high temp Extra sensor 2
VentSettings.Cor_ExtraS
ensor3HighLimit
R
40491
30
Settings, Alarm limits
Alarm limit high temp Extra sensor 3
VentSettings.Cor_ExtraS
ensor4HighLimit
R
40492
30
Settings, Alarm limits
Alarm limit high temp Extra sensor 4
VentSettings.Cor_ExtraS
ensor5HighLimit
R
40493
30
Settings, Alarm limits
Alarm limit high temp Extra sensor 5
VentSettings.Cor_ExtraS
ensor1LowLimit(0)
R
40494
10
Settings, Alarm limits
Alarm limit low temp Extra sensor 1
VentSettings.Cor_ExtraS
ensor2LowLimit
R
40495
10
Settings, Alarm limits
Alarm limit low temp Extra sensor 2
VentSettings.Cor_ExtraS
ensor3LowLimit
R
40496
10
Settings, Alarm limits
Alarm limit low temp Extra sensor 3
VentSettings.Cor_ExtraS
ensor4LowLimit
R
40497
10
Settings, Alarm limits
Alarm limit low temp Extra sensor 4
VentSettings.Cor_ExtraS
ensor5LowLimit
R
40498
10
Settings, Alarm limits
Alarm limit low temp Extra sensor 5
VentSettings.Cor_FilterG
uard1Limit
R
40499
100
Settings, Alarm limits
Alarm limit filter guard 1 (Pa)
VentSettings.Cor_FilterG
uard2Limit
R
40500
100
Settings, Alarm limits
Alarm limit filter guard 2 (Pa)
VentSettings.Cor_FilterG
uard1Limit_X1
R
40501
1000
Settings, Alarm limits
Alarm limit filter guard 1 X1 (m
3
/h)
VentSettings.Cor_FilterG
uard1Limit_Y1
R
40502
50
Settings, Alarm limits
Alarm limit filter guard 1 Y1 (Pa)
VentSettings.Cor_FilterG
uard1Limit_X2
R
40503
2000
Settings, Alarm limits
Alarm limit filter guard 1 X2 (m
3
/h)
VentSettings.Cor_FilterG
uard1Limit_Y2
R
40504
150
Settings, Alarm limits
Alarm limit filter guard 1 Y2 (Pa)
VentSettings.Cor_FilterG
uard2Limit_X1
R
40505
1000
Settings, Alarm limits
Alarm limit filter guard 2 X1 (m
3
/h)
VentSettings.Cor_FilterG
uard2Limit_Y1
R
40506
50
Settings, Alarm limits
Alarm limit filter guard 2 Y1 (Pa)