CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

64 Chapter 6 Input Status Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentActual.Cor_AlaPt(47)
L
10079
Alarm
Points
Manual fire damper
VentActual.Cor_AlaPt(48)
L
10080
Alarm
Points
Internal battery error
VentActual.Cor_SAFStart1(0)
L
10081
SAF/EAF
Pressure
and Flow
Start signal full speed supply air fan
VentActual.Cor_EAFStart1
L
10082
SAF/EAF
Pressure
and Flow
Start signal full speed extract air fan
VentActual.Cor_SAFStart2
L
10083
SAF/EAF
Pressure
and Flow
Start signal half speed supply air fan
VentActual.Cor_EAFStart2
L
10084
SAF/EAF
Pressure
and Flow
Start signal half speed extract air fan
VentActual.Cor_HeatPumpStart(0)
L
10085
Actual/Set
point
Start signal Heat Pump
VentActual.Cor_ExchPumpStart
L
10086
Actual/Set
point
Start signal Exchanger
VentActual.Cor_CoolPumpStart
L
10087
Actual/Set
point
Start signal Cool Pump
VentActual.Cor_SAFFrequencyStart
L
10088
SAF/EAF
Pressure
and Flow
Start signal frequencer supply air fan
VentActual.Cor_EAFFrequencyStart
L
10089
SAF/EAF
Pressure
and Flow
Start signal frequencer extract air fan
VentActual.Cor_AlaPt(49)
L
10090
Alarm
Points
Sensor error supply air temp.
VentActual.Cor_AlaPt(50)
L
10091
Alarm
Points
Sensor error extract air temp.
VentActual.Cor_AlaPt(51)
L
10092
Alarm
Points
Sensor error room temp. 1
VentActual.Cor_AlaPt(52)
L
10093
Alarm
Points
Sensor error room temp. 2
VentActual.Cor_AlaPt(53)
L
10094
Alarm
Points
Sensor error extract air temp.
VentActual.Cor_AlaPt(54)
L
10095
Alarm
Points
Sensor error extra sensor
VentActual.Cor_AlaPt(55)
L
10096
Alarm
Points
Sensor error SAF pressure
VentActual.Cor_AlaPt(56)
L
10097
Alarm
Points
Sensor error EAF pressure