CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

70 Chapter 6 Input Status Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentActual.Cor_AlaPt(118)
L
10204
Alarm
Points
Motor control 2 in manual mode
VentActual.Cor_AlaPt(119)
L
10205
Alarm
Points
Communication error expansion unit
3
VentActual.Cor_AlaPt(120)
L
10206
Alarm
Points
Communication error expansion unit
4
VentActual.Cor_AlaPt(121)
L
10207
Alarm
Points
Low outdoor air temp.
VentActual.Cor_AlaPt(122)
L
10208
Alarm
Points
High outdoor air temp.
VentActual.Cor_AlaPt(123)
L
10209
Alarm
Points
Malfunction adiabatic cooling
VentActual.Cor_AlaPt(124)
L
10210
Alarm
Points
Communication error expansion unit
5
VentActual.Cor_AlaPt(125)
L
10211
Alarm
Points
Communication error expansion unit
6
VentActual.Cor_DIReserved(0)
L
10212
Not used
Not used
VentActual.Cor_DIReserved(0)
L
10213
Not used
Not used
VentActual.Cor_DIReserved(0)
L
10214
Not used
Not used
VentActual.Cor_DIReserved(0)
L
10215
Not used
Not used
VentActual.Cor_DIReserved(0)
L
10216
Not used
Not used
VentActual.Cor_ExpPDT1UDi1(0)
L
10217
Digital
inputs
Value of UDI1 expansion unit 3
VentActual.Cor_ExpPDT1UDi2
L
10218
Digital
inputs
Value of UDI2 expansion unit 3
VentActual.Cor_ExpPDT2UDi1
L
10219
Digital
inputs
Value of UDI1 expansion unit 4
VentActual.Cor_ExpPDT2UDi2
L
10220
Digital
inputs
Value of UDI2 expansion unit 4
VentActual.Cor_ExpPDT3UDi1(0)
L
10221
Digital
inputs
Value of UDI1 expansion unit 5
VentActual.Cor_ExpPDT3UDi2
L
10222
Digital
inputs
Value of UDI2 expansion unit 5
VentActual.Cor_ExpPDT3UDi1
L
10223
Digital
inputs
Value of UDI1 expansion unit 6
VentActual.Cor_ExpPDT3UDi2
L
10224
Digital
inputs
Value of UDI2 expansion unit 6