72 Chapter 7 Frequency converters
Chapter 7 Frequency converters
Version 3.4 of Corrigo ventilation supports the frequency converters listed below:
Vacon NXL
Lenze
Omron V1000
Emerson Commander
LS
EBM
Danfoss FC 101
ABB ACS
EC Blue
When communicating via frequency converters through Modbus, it is sometimes necessary to change
certain settings in the frequency converter.
Two parallel connected frequency converters for supply air and two parallel connected frequency
converters for extract air can be run. The supply air fan will have address 1 and the parallel supply air
fan address 3. The extract air fan will have address 2 and the parallel extract air fan address 4.
Below is described what settings are necessary in the various models:
Vacon NXL
No settings necessary. Vacon NXL frequency converters are controlled via Modbus. Communication,
alarms and certain indications can be read.
The following signals can be read/written from/to the frequency converter:
Address
Modbus register
Name
Scaling
Type
2003
32003, 42003
FB Speed reference (SP)
1000
%
2001
32001, 42001
FB Status word
-
Binary
11
30011, 40011
Acc. Motor output
1
kW
80
30080, 40080
Amount of decimals for Acc. Motor
output
1
kWh
2103
32103, 42103
FB Motor speed
100
%
2105
32105, 42105
Motor speed
1
+/- Rpm
2106
32106, 42106
Current
100
A
2107
32107, 42107
Torque
10
+/- % (of nominal)
1501
31501, 41501
Output
1000
kW
2110
32110, 42110
DC voltage
1
V
2111
32111, 42111
Active error
-
Error code
2101
32101, 42101
FB Status word
-
Binary
The variables presented in the display of the Corrigo are:
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh).