CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 7 Frequency converters 73
Lenze
No settings necessary.
Lenze frequency converters are controlled via Modbus. Communication, alarms and certain
indications can be read.
The following signals can be read/written from/to the frequency converter:
Address
Modbus register
Name
Scaling
Type
49
32049, 42049
Password
-
-
50
32050, 42050
Parameter version
-
-
45
30045, 40045
FB Speed reference (SP)
50
%
2
30002, 40002
FB Status word
-
Binary
512
32512, 42512
Acc. Motor output
1
kW
528
32528, 42528
Motor frequency
10
Hz
509
32509, 42509
Current
1
A
511
32511, 42511
Output
1000
kW
506
31506, 41506
DC voltage
1
V
30
32110, 42110
Active error
-
Error code
27
32027, 42027
FB Status word
-
Binary
The variables presented in the display of the Corrigo are:
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh).
Omron V1000
Connected via RS485:
R+ is connected to S+
R- is connected to S-
R+/S+ is connected to B on port 1 or 2
R-/S- is connected to A on port 1 or 2
Parameters
The following parameters must be set from the display of the frequency converter:
H5-01 (0x425): Slave address, set to = 1 for Supply air fan and = 2 for Exhaust air fan
H5-07 (0x42B): RTS Control, set to = 1 (enabled) for activation of RS485
o1-03 (0x502): Frequency reference units, set to = 1 for 0-100%.
H5-03 (0x427): Parity, set to = 0 (no parity)
Default values should be used for remaining parameters. The following values may not be changed:
H5-02 (0x426): Communication speed, default =3 (9600)
H5-04 (0x428): Stopping method after communication error, default = 3 (no stop)
H5-11 (0x43C): Communication Enter Function, default=1 (Enter command not
necessary)
H5-12 (0x43D): Run command, default=0 (bit 0=forward start/stop, bit 1= reverse
start/stop)
b1-01 (0x180): Frequency Reference selection 1, default = 2 (via Modbus)
b2-01 (0x181): Run command selection 1, default = 2 (via Modbus)