TOPVEX SF Installation instruction 130324 CEA006

Installation |
9
5.3.1 Mounting brackets
Together with the Topvex SF unit follows 4 mounting brackets that allows the unit to be mounted according to illustra-
tion figure 3 and figure 4.
D
30
A
B
C
Fig. 4
Model
A B C D
Topvex Topvex SF02EL/HW
563 523 603 1235
Topvex Topvex SF03 EL/HW
626 586 666 1322
Topvex Topvex SF04 EL/ HW
756 716 796 1322
Topvex Topvex SF06 EL/ HW
856 816 896 1322
Topvex Topvex SF08 HW 911 871 951 1322
Topvex Topvex SF12 HW 1017 977 1057 1371
5.3.2 Installing procedure
Warning
Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is used.
Use protective clothing.
1 Prepare the surface where the unit is to be mounted.
Make sure that the surface is flat, levelled and that it
carries the weight of the unit. Perform the installation
in accordance with local rules and regulations.
2 Lift the unit in place.
3 Connect the unit electrically to the power supply
through the all pole circuit breaker, safety switch (ac-
cessory). The wiring is led directly to the electrical
connection box.
See enclosed wiring diagram, and chapter 5.4.3 for
more information.
Warning
The units electrical connection to the power supply must be preceded by an all pole circuit breaker with a
minimum 3 mm gap.
Danger
Make sure that the power supply to the unit is disconnected before performing any maintenance or
electrical work!
All electrical connections must be carried out by an authorized installer and in accordance with local rules
and regulations.
130324 | A006