Chiller SyScroll 20 to 35 Air NEW Air Cooled Water Chillers Cooling Only and Condensing unit Engineering Data Manual 20.0 to 33.
SyScroll 20-35 Air | Key points R410A refrigerant. Simpler refrigerant circuit layout with only one compressor. Great accessibility to internal components for service operations. Aeraulic independence between refrigerant circuit and condensing side. New display on external panel allowing the complete control of the unit. Wide operating limits. Low water temperature applications in cooling mode (down to -8 °C). Improved acoustic performances. New fan motor with integrated grill & condenser.
| SyScroll 20-35 Air Specifications CO = Cooling Only; RE = Remote Evaporator; General The new SyScroll Air air cooled water chillers have been designed and optimized to operate with R410A refrigerant fluid. They are available in cooling only CO and remote evaporator (RE) versions. Each version consists of 4 sizes and covers a nominal cooling capacity range from 20.0 to 33.0 kW. All units are equipped with one scroll compressors.
SyScroll 20-35 Air | Condenser fans Units are equipped with two 500mm diameter axial fans with profiled, sickle shaped blades designed with bionical know how, optimized full bellmouth with static blades (motor suspension) and short diffusor. They are placed directly in front of the coil in order to increase the air flow and the heat transfer between air and refrigerant. Fan motors have IP54 protection grade, and thermostat protection placed in the bearings. Both fans are equipped with a safety grill.
| SyScroll 20-35 Air Factory-installed option: Coil with “E-Coating” treatment, Soft starter, Electronic Expansion Valve, Coil guard, Desuperheater. Field-installed accessories Compressor jacket, Mechanical Gauge kit, Hydro kit (112 l water tank), Water flow switch, Water pressure switch, In/out valve kit, Remote On/Off control, ModBus protocol kit for BMS, Power factor correction capacitors, Sequencer for up to 4 chillers installation, Remote terminal.
SyScroll 20-35 Air | Accessories & Options SyScroll Air Delivery Abbreviation Description & Benefit Sequence phases control Std PHC It allows to check the correct sense R-S-T of electric supply phases for 400/3/50 units. Control circuit transformer 230V/12V Std TRF Voltage transformer to provide correctly the separated voltage to the auxiliary line. Main switch Std Front operated switch-disconnector with direct mounted handle to cut the power Supply Line according CE standards.
| SyScroll 20-35 Air EN 14511-2011 Starting 2012 Campaign Eurovent Certification Company took decision to start certify only performances declared in according severe European Standard EN14511. BEFORE 2012: GROSS PERFORMANCES Before this date all capacity performances are declared, measured and certified by Eurovent, as GROSS performances.
SyScroll 20-35 Air | Refrigerant Flow Diagram - Syscroll 20-35 Air CO ST 2 KM S A AT 1 B S S KM EEV CONTROL F D C L 3 4 6 UNIT CONTROL 5 ELECTRONIC EXPANSION VALVE (OPTIONAL) 7 MECHANICAL EXPANSION VALVE (STANDARD) 3 BT 15 4 N E 5 S N FS 12 HYDROKIT L 13 11 9 10 14 8 13 COMPONENTS 1 Compressor scroll type 2 Air cooled condenser 3 Filter drier 4 Sight glass 5 Expansion valve 6 Plate heat exchanger 7 Pump 8 Drain valve 9 Water buffer tank 10 Water filter (loose) 11 Automati
| SyScroll 20-35 Air Refrigerant Flow Diagram - Syscroll 20-35 Air RE 2 KM S A AT 1 B S KM 3 D 3 COMPONENTS 1 Compressor scroll type 2 Air cooled condenser 3 Global Valve SAFETY/CONTROL DEVICES A High pressure switch (42 bar) AT High pressure transducer B Low pressure switch (1,5 bar) D Air temperature sensor S Shrader valve (service/charging point) KM Manometer (optional) ↓ Pipe connection with Shrader valve 1/4” SAE ---- Optional components
SyScroll 20-35 Air | Operating Limits Operating limits Syscroll 20-35 Air Model Water Chilled liquid Liquid outlet temperature Brine Temperature spread Maximum operating pressure Heated liquid Outdoor air Leaving water temperature Water Temperature spread Maximum operating pressure Outdoor air temperature (cooling) Power supply voltage °C +5 to +18 °C -8 / +5 (with glycol and electronic expansion valve); +5/+18 (standard application) K 3 to 7 bar 3 °C +25 to +55 °C 3 to 15 bar 3 °C
| SyScroll 20-35 Air Performances corrective factors (brine) Unit capacity, absorbed power, brine flow rate, brine pressure drop, have to be corrected according following formula: CORRECTED UNIT CAPACITY QCORRECTED/GLYCOL = QNOMINAL x Kc x KcE,P Where Kc : Capacity corrective factor according to LWT (ΔT = 5 [K]) → refer to Table 1 KcE : Capacity corrective factor according to glycol percentage (ETHYLENE GLYCOL) → refer to Table 2 KcP : Capacity corrective factor according to glycol percentage (PROPYLE
SyScroll 20-35 Air | Table 2 0% 10% 20% 30% 35% 40% Freezing point (*) °C 0 -4 -10 -10 -21 -21 Minimum leaving water temperature allowed °C 6 2 -2 -2 -8 -8 Capacity corrective factor (**) KcE 1 0,995 0,985 0,985 0,963 0,963 Absorbed power corrective factor (**) KiE 1 0,998 0,995 0,995 0,983 0,983 Flow rate corrective factor KfE 1 1,015 1,050 1,050 1,123 1,123 Pressure drop corrective factor (***) KpE 1 1,070 1,160 1,160 1,283 1,283 Ethylene Glycol Perce
| SyScroll 20-35 Air Technical data - SyScroll 20-35 Air CO 20 25 30 35 Cooling Capacity (2) Data @ Eurovent LCP/W/P/C AC conditions (1) kW 20,4 23,9 27,7 33,2 Cooling Capacity (3) kW 20,8 24,4 28,2 33,7 Input Power (2) kW 7,12 7,88 9,47 12,0 Input Power (3) kW 6,67 7,41 8,97 11,5 EER 100% (2) kW/kW 2,87 3,03 2,93 2,77 EER 100% (3) kW/kW 3,12 3,29 3,14 2,93 A A A B EUROVENT CLASS EER 75% (3) kW/kW 3,48 3,67 3,59 3,32 EER 50% (3) kW/kW 3,70 3,92 3,85
SyScroll 20-35 Air | Technical data - SyScroll 20-35 Air RE Data conditions (1) Cooling Capacity (1) Input Power (1) EER 100% 20 25 30 35 kW 22,1 26,4 29,9 36,2 kW 7,23 7,96 9,56 12,3 kW/kW 3,06 3,32 3,13 2,94 Number of Refrigerant Circuits Part Load Steps 1 % 0-100 Power Supply 400V/3+N/50Hz Startup Type Maximum Absorbed Power Direct (softstarter as option) kW 10 12 13 Maximum Corrent (FLA) A 20 25 26 16 35 Startup Corrent (LRA) A 105 115 122 144 90 90 Refrigera
| SyScroll 20-35 Air Electrical Data - SyScroll 20-35 Air Compressor Data 400V/3/50Hz NOMINAL MAXIMUM PNOM-CPS INOM-CPS PMAX-CPS IMAX-CPS FLA ISTARTUP-CPS LRA Size kW A kW A A PFC (NOM) PFC* 20 6,3 12 8,6 16 25 7,1 13 10,2 21 101 0,78 > 0.90 111 0,80 30 8,7 15 11,9 > 0.90 22 118 0,83 35 11,3 19 14,8 > 0.90 31 140 0,85 > 0.
SyScroll 20-35 Air | Cooling Capacities - Syscroll 20-35 Air CO OAT (°C) Model LWT °C 25 SYSCROLL 25 CO SYSCROLL 30 CO SYSCROLL 35 CO 32 35 38 40 42 45 48 50 PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* kW SYSCROLL 20 CO 30 kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW 5 22,1 4,87 20,8 5,34 20,2 5,56 19,3 5,90 18,3 6,25 17,6 6,50 16,9 6,78 15,7 7,21 14,5 7,64 13,8 7,92 7 23,3 4,98 2
| SyScroll 20-35 Air Cooling Capacities - Syscroll 20-35 Air RE OAT (°C) Model Te °C 25 SYSCROLL 25 RE SYSCROLL 30 RE SYSCROLL 35 RE 32 35 38 40 42 45 48 PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* kW SYSCROLL 20 RE 30 kW kW kW 1 23,8 4,32 22,3 4,73 21,8 4,89 20,8 kW kW kW kW kW 5,2 19,7 5,51 18,9 5,74 18,1 5,95 17,0 6,25 16,1 6,51 kW kW kW kW kW kW kW kW kW 3 24,3 4,59 22,8 5,03 22,2 5,20 21,2 5,5
SyScroll 20-35 Air | Pump Available Static Pressure 220 200 180 P (kPa) 160 20-25 140 30-35 120 100 80 60 40 20 0,00 0,25 0,50 0,75 1,00 1,25 1,75 2,00 2,25 2,50 1,50 1,75 2,00 2,25 2,50 1,50 1,75 2,00 2,25 2,50 1,50 G (l/s) Water Circuit Pressure Drop 70 60 P (kPa) P (kPa) 50 70 40 60 30 50 20-25 30-35 20-25 30-35 20 40 10 30 0 20 0,00 0,25 0,50 0,75 1,00 10 1,25 G (l/s) 0 35 0,50Drop 0,75 Water0,00 Filter*0,25 Pressure 1,00 30 1,25 G (l/s) P (kPa) P (kPa)
| SyScroll 20-35 Air Dimensions SyScroll 20-35 Air Front view F Side view Rear view G O F G N E O B B N D C E A 31 LIFT LIFT R A Q 31 D C 32 LIFT R LIFT P3 Q P1 32 Top view P1 P3 P2 31 P4 1441 P4 P2 31 20 1441 NOTES A Water inlet ø 1 1/4” MGT B Water outlet ø 1 1/4” MGT C Auxiliary lines D Electrical power supply E Gauge kit (optional) F Main switch G Control keypad/display N Desuperheater water inlet 1" Gas M O Desuperheater water Outlet 1" Gas M Q Liquid Line ø 1/2" R
SyScroll 20-35 Air | Dimensions Hydrokit 20-35 Front view Side view Rear view B F G 292 2005 10 O E A 75 D C 31 A D 186 390 C R 1480 92 287 LIFT LIFT 250 305 B 860 N Q 32 Top view P2 31 1441 P4 60 NOTES A Water inlet ø 1 1/4” MGT B Water outlet ø 1 1/4” MGT C Tank fill ø 1 1/2” MGT D Water drain ø 3/8” FGT 9 1360 1480 P2 60 26 P4 P1 457 509 P3 26 P1 P3 21
| SyScroll 20-35 Air Weight Distribution Weight distribution Model Size SYSCROLL 20-35 Air CO SYSCROLL 20-35 Air CO + Hydrokit SYSCROLL 20-35 Air RE P1 P2 P3 P4 Operating weight Shipping weight kg kg kg kg kg kg P1-P4 coordinates CG coordinates a b x y mm mm mm mm 20 54 59 64 69 248 254 457 1.441 264 680 25 62 65 74 77 279 285 457 1.441 260 676 30 62 66 76 79 283 289 457 1.441 260 669 35 68 68 81 81 298 304 457 1.
Tel. +39 0362 680 1 Fax +39 0362 680 693 info@systemair.it www.systemair.com Systemair · November 2018 · EDM SYSCROLL 20-35 AIR-S-6GB/11.18 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.