EDM WQL H RC 524 1604

WQL/WQH/WQRC 524-1604
|
11
Operating Limits
Note: Maximum % glycol (ethylenic or propilenic): 40%.
WQL/WQH 524 to 1604 - R410A
Chilled
liquid
Leaving uid
temperature range
Water
°C
+5 to +18
Brine °C
-8 / +5 (with glycol and electronic expansion valve);
+5/+18 (standard application)
Temperature spread
°K
3 to 8
Maximum operating pressure
bar
6
Heated
liquid
Leaving uid
temperature range
Water
°C
+25 to +55
Temperature spread
°K
3 to 15
Maximum operating pressure
bar
6
Unit power supply
V/ph/Hz
400/3/50
20
25
30
35
40
45
50
55
60
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20
Evaporator leaving water temperature (°C)
Water
+
Glycol
Water
Condenser leaving water temperature (°C)
Note: Maximum % glycol (ethylenic or propilenic): 40%.
WQRC 524 to 1604 - R410A
Liquid
Leaving uid
temperature range
Water
°C
+5 to +18
Brine °C
-8 / +5 (with glycol and electronic expansion valve);
+5/+18 (standard application)
Temperature spread
°K
3 to 8
Maximum operating pressure
bar
6
Condensing temperature °C +30 to +58
Unit power supply
V/ph/Hz
400/3/50
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20
25
30
35
40
45
50
55
60
Water
+
Glycol
Water
Evaporator leaving water temperature (°C)
Condensing temperature (°C)