WQL 524 604 704 804 904 1004 1104 1204 1404 1604
DESUPERHEATER
Number/Type 2 / Plate
Heat recovery kW 22,1 28,4 36,1 42,0 50,4 68,3 78,1 81,9 102 112
Water flow rate l/s 1,05 1,35 1,73 2,01 2,41 3,26 3,73 3,91 4,86 5,37
Water pressure drop kPa 8,3 4,5 5,1 5,7 5,0 8,7 10,3 7,5 14,08 10,73
WEIGHT
Shipping Weight (4) kg 858 929 1.110 1.279 1.266 1.363 1.449 1.541 1.611 1.660
Shipping Weight (5) kg 961 1.032 1.213 1.382 1.369 1.466 1.552 1.644 1.714 1.763
Operating Weight (4) kg 890 971 1.156 1.329 1.340 1.453 1.552 1.660 1.743 1.798
Operating Weight (5) kg 993 1.074 1.259 1.432 1.443 1.556 1.655 1.763 1.846 1.901
DIMENSIONS
Length mm 2.250
Width mm 850 (4) / 854 (5) / 885 (4)/(6) - 1.005 (5)/(6)
Height mm 1.845 (4) / 1.880 (5)
ACOUSTIC DATA
Sound Power Level (4) / (5) dB(A) 81/75 82/76 85/79 87/81 89/83 90/84 90/84 90/84 92/86 94/88
Sound Pressure Level (4)* / (5)* dB(A) 49/43 50/44 53/47 55/49 57/51 58/52 58/52 58/52 60/54 62/56
(1) According to EN14511 standard: Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser EWT/LWT 30°C/35°C (without water pump).
(2) According to EN14825 standard and following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers.
(3) Data for each refrigerant circuit.
(4) STD version.
(5) S version.
(6) Only for movimentation.
(*) Sound pressure level at 10 m. Values refers to ISO Standard 3744 with parallepiped shape.