EDM WQL H RC 524 1604
WQL/WQH/WQRC 524-1604
|
17
WQH 524 604 704 804 904 1004 1104 1204 1404 1604
EXTERNAL HEAT EXCHANGER WATER CONNECTIONS
Type Victaulic
Inlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4” 4" 4"
Outlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4” 4" 4"
EXTERNAL HEAT EXCHANGER PUMP
Number 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Input Power/SP kW 2,20 3,00 3,00 4,00 4,00 5,50 5,50 5,50 7,50 11,00
Available Static Pressure/SP kPa Refer to “4B - Pump Av. Static Pressure”
Input Power/HP kW 3,00 4,00 5,50 5,50 5,50 5,50 7,50 7,50 - -
Available Static Pressure/HP kPa Refer to “4B - Pump Av. Static Pressure”
DESUPERHEATER
Number/Type 2 / Plate
Heat recovery kW 22,1 28,4 36,1 42 50,4 68,3 78,1 81,9 97 106
Water flow rate l/s 1,05 1,35 1,73 2,01 2,41 3,26 3,73 3,91 4,65 5,08
Water pressure drop kPa 8,3 4,5 5,1 5,7 5 8,7 10,3 7,5 12,86 9,59
WEIGHT
Shipping Weight (6) kg 876 947 1.141 1.311 1.302 1.410 1.494 1.585 1.655 1.704
Shipping Weight (7) kg 979 1.050 1.244 1.414 1.405 1.513 1.597 1.688 1.758 1.807
Operating Weight (6) kg 909 989 1.187 1.360 1.376 1.500 1.598 1.704 1.787 1.842
Operating Weight (7) kg 1.012 1.092 1.290 1.463 1.479 1.603 1.701 1.807 1.890 1.945
DIMENSIONS
Length mm 2.250
Width mm 850 (6) / 854 (7) / 885 (6)/(8) - 1.005 (7)/(8)
Height mm 1.845 (6) / 1.880 (7)
ACOUSTIC DATA
Sound Power Level (6) / (7) dB(A) 81/75 82/76 85/79 87/81 89/83 90/84 90/84 90/84 92/86 94/88
Sound Pressure Level (6)* / (7)* dB(A) 49/43 50/44 53/47 55/49 57/51 58/52 58/52 58/52 60/54 62/56
(1) According to EN14511 standard: Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser EWT/LWT 30°C/35°C (without water pump).
(2) According to EN14825 standard and following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers
(3) According to EN14511 standard: Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 40°C/45°C.
(4) According to EN14825 standard - low temperature application (35°C) and following COMMISSION REGULATION (EU) No 813/2013 for heat pumps.
(5) According to EN14825 standard - medium temperature application (55°C) and following COMMISSION REGULATION (EU) No 813/2013 for heat pumps.
(6) STD version.
(7) S version.
(8) Only for movimentation.
(9) Data for each refrigerant circuit.
(*) Sound pressure level at 10 m. Values refers to ISO Standard 3744 with parallepiped shape.