EDM WQL H RC

WQL-WQH-WQRC 20-190
|
5
Safety
Each unit is equipped with following electrical / refrigerant / hydraulic safety
devices :
Door lock main isolating switch
Phase monitor control
High pressure switch with manual reset
Discharge safety valve
Low pressure switch with automatic / manual reset
Anti-freeze probe (leaving water temperature)
Differential pressure switch (source / plant side)
Standards
WQL/WQH/WQRC are built in compliance with following standards :
Machinery Directive : 2006/42/EC
Low Voltage Directive : 2006/95/EC
Electromagnetic Compatibility Directive : 2014/30/EU
Pressure Equipment Directive : 2014/68/EU
And following harmonized European standards :
Safety of machinery - Basic concepts, general principles for design: UNI
EN ISO 12100-1 / 2
Safety of machinery - Safety Distances To Prevent Hazard Zones Being
Reached By Upper And Lower Limbs : EN ISO 13857
Safety of machinery - Electrical equipment of machines : EN 60204-1
Low-voltage switchgear and controlgear assemblies : EN 60439-1
Electromagnetic compatibility (EMC) - Immunity for industrial
environments : IEC EN 61000-6-2
Electromagnetic compatibility (EMC) - Emission standard for residential,
commercial and light-industrial environments : IEC EN 61000-6-3
Refrigerating systems and heat pumps. Safety and environmental
requirements : EN 378-1 / 2
Metallic products - Types of inspection documents : EN 10204
Copper and copper alloys. Seamless, round copper tubes for air
conditioning and refrigeration : BS EN 12735-1 / 2
Pressure equipment for refrigerating systems and heat pumps. General
requirements : BS EN 14276-1 / 2
Refrigerating systems and heat pumps - Pressure relief devices and their
associated piping - Methods for calculation : BS EN 13136
Metallic industrial piping : BS EN 13480-3
Factory installed options
ModBus protocol kit for BMS
Compressor soft starter
Power factor correction capacitors
Electronic expansion valve
Compressor overload protection (only for F2 units)
Automatic circuit breaker (only for F2 units)
Condensing control kit
Electric heater wiring kit
Additional heating device wiring kit
Mechanical gauges kit
Compressor jacket
On board hydrokit (1P/both exchangers/SP for F1 units, 1P/2P/both
exchangers/SP-HP for F2 units)
Desuperheater (only for F2 units)
Field installed accessories
Remote ON-OFF
Remote keyboard panel
Sequencer up to 4 units
Condensing control kit
Water temperature sensor for DHW tank
Outdoor air sensor for weather compensation
Electric heater wiring kit
Additional heating device wiring kit
Pressostatic water valve for well application (only for F1 units)
Compressor jacket
Flow switch
Pressure switch
Victaulic to threaded pipe connection
3-way valve for DHW production
Spring type anti-vibration mounts (only for F2 units)
Water filter
Valves IN/OUT (only for F1 units)