DataSheet OPTIMA RS201309

Air volume control
|
1 / 7
OPTIMA-RS
Single skin VAV units - round inlet and rectanglar oulet
Description
Single skin round to square VAV terminal units is
common ly used for supply air applications or for return
air applica tions at low to medium system pressures.
Optima-RS VAV terminal units are ideal for multizone
control with supply and return in master and slave setup
such as ofces, hotel rooms or meeting rooms where the
required cooling and heating load will vary on demand.
Highlights:
Damper tightness class 4 according to EN 1751
Casing tightness class C according to EN 1751
High measuring accuracy of 5%
Air volume range of 57 to 5881 m
3
/h
Operating range of up to 1000 Pa
30 mm high density insulation with cleanable
protection tissue cover
Accessories for Optima-RS:
Attenuators Optima-ASA
Silencers are available to reduce the discharge sound
power levels when required. Multi-outlet insulated
terminal units are available when multi-zone application
is required.
Ordering codes:
Ordering code example:
Optima-RS - 16 - BLC4 - 160 - 800
Optima-RS, inlet size 160, Belimo LMV-D3 drive/controller, V
min
160 m³/h,
V
max
800 m³/h, control voltage DC 2-10 V
NOTES:
1. If the air volumes are not given during the ordering process, then stan-
dard Factory setting will be applied according to table
2. V
min
can also be set to 0 m
3
/h if required by demand upon ordering
3. The setup values of V
min
and V
max
must be inside the range of min / max
factory settings (see dimensions / volumes table)
4. The standard input signal on the controller is set to 2-10 V, upon request
0-10 V can also be selected
Optima-RS -
Size (mm) 10 - 40 (øD-100 to øD-400)
Drive /
controller type
BLC1
BLC4
BLC1MOD
BLC1LON
GO
GOMOD
BELIMO L(N) MV-D3, MPBUS
BELIMO L(N) MV-D3
BELIMO L(N) MV-D3, MODBUS
BELIMO L(N) MV-D3, LON
Optima-GO
Optima-GO, MODBUS
V
min
(m
3
/h)
V
max
(m
3
/h)
Control voltage
(DC 0 - 10 V)
(DC 2 - 10 V)
0
2
Insulation I