Corrigo ventilation 3.4 manu

108 Chapter 17 Configuration Manual Corrigo Ventilation, revision R
17.31.3 Automatic summer-/wintertime change-over
When Corrigo is set on automatic summertime/wintertime change-over, the timer will automatically
change between summertime and wintertime according to European standard.
Automatic summer/
winter time
change-over
Yes
17.31.4 Address
Corrigo uses the addresses below when connecting to E tool
©
, and when multiple controllers are
connected in an EXO network. E tool
©
normally uses the addresses below, so if an address is
changed, the new address must also be entered in E tool
©
. If several Corrigo are connected in a
network, all the units must have the same ELA address, but each unit must have a unique PLA
address.
Address
PLA: 254
ELA: 254
17.31.5 Display anywhere (remote control)
If multiple Corrigo units are connected in a network, it is possible to remote control a unit in the
network from a unit with display. You do this by entering the address of the unit you wish to remote
control in the unit with display. The function is aborted by pressing the buttons UP, OK and DOWN
simultaneously.
Address for
remote communication
(PLA:ELA) : 00:00
17.31.6 Automatic logoff
If the access level is Operator, Service or Admin, the user will automatically be logged off to
Normal after a settable time of inactivity. The time is settable in units of 5 seconds. Standard 60
units = 5 minutes.
The automatic logoff can be removed, see 8.4.
Time before user
is automatically
logged off:60
(Unit 5 s)
17.31.7 Activation of start-up wizard
The start-up wizard is a special program which at the first start-up guides the operator through a
number of start-up menus where you set certain operation parameters. For more information, see the
section Start-up wizard.
Activate wizard
No