76 Chapter 15 Settings Manual Corrigo Ventilation, revision R
Chapter 15 Settings
In this menu group all settings for all activated functions should be available. The menu group is
only available when logging on as Admin. Depending on what choices have been made during
configuration, some of the alternatives in this menu group may not be shown.
Settings
Control temp
Control pressure
Control flow
Control humidity
Control CO2
Control extra unit
Alarm settings
15.1 Control temp
Supply air controller
Supply air control
P-band: 33.0 °C
I-time: 100.0 sec
The set P-band for the supply air controller is for the whole controller signal. This means that the P-
band for each sequence is proportionate to the split percentage values given to sequences.
For example:
P-band for the supply air controller is set to 33 K. The split is set so that cooling gets 0…30 % = 30
%, the exchanger gets 32…50 % = 18 % and the heater gets 54…100 % = 46 %.
The individual P-bands will then be:
Chiller: 30 % of 33°C = 10°C
Exchanger: 18 % of 33°C = 6°C
Heating: 46 % of 33°C = 15°C
The remaining 2°C are the neutral zone between cooling and exchanger and between exchanger and
heating.
The split values are set in the configuration submenu Other parameters.
If cascade control
max/min supply setp
Max: 30°C
Min: 12°C
Room controller
Room control
P-band: 100.0 °C
I-time: 300.0 s
Extract air controller
Extract air control
P-band: 100.0 °C
I-time: 300.0 s