80 Chapter 15 Settings Manual Corrigo Ventilation, revision R
Alarm delay, exchanger efficiency
Low efficiency
30 min
Alarm delay, fan malfunction (SAF and EAF)
Alarm delay
malfunction
SAF: 120 s
-----------------------
EAF: 120 s
Alarm delay, pump malfunction
Alarm delay malfunc
P1 heating: 5 s
P1 cooling: 5 s
P1 exchan: 20 s
Alarm delay, misc.
Filter guard1: 180 s
Filter guard2: 180 s
Flow switch: 5 s
Frost prot: 0 s
Ext. Frost prot. DI refers to the digital input signal Deicing Heat exchanger.
Alarm delay, misc. 2
Alarm delay
Deicing DI: 0 s
Fire alarm: 0 s
Ext alarm: 0 s
Frost protection DI refers to the digital input signal De-icing thermostat exchanger.
Alarm delay, misc. 3
Alarm delay
Elec. heat: 0 s
Sensor error: 5 s
Rot sent exch: 20 s
15.6.3 Restore alarm
Service alarm
(Filter alarm)
Time counter set
to zero: No
15.7 Save and restore settings
Restore factory
settings: No
Restore user
settings: No
In this menu, it is possible to restore all parameters to their factory settings or to the user settings
they were saved as earlier, see below.
Save user settings
No
The present configuration can be saved in a separate memory area and can later be restored using
the previous menu, "Restore user settings".