56 Chapter 5 Holding Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_FanTy
pe
X
40475
0
Settings, General
Select fan control mode:
0=1-Speed.
1=2-Speed.
2=Frequency control pressure
3=Frequency control air flow
4=Frequency control manually
5=Direct frequency control
6=Frequency control with slave
controlled EAF
7=Frequency control with slave
controlled EAF air flow depending
8=Frequency control with slave
controlled SAF
9=Frequency control with
slave controlled SAF air flow
depending
VentSettings.Cor_HeatTy
pe
X
40476
0
Settings, General
Type of heating:
0=Water
1=Electric
2=Not connected
3=Both water and electric
VentSettings.Cor_CoolTy
pe
X
40477
0
Settings, General
Type of cooling:
0=Water
1=DX
2=Not connected
3=DX with exchange control
VentSettings.Cor_ExchT
ype
X
40478
2
Settings, General
Type of heat exchanger:
0=Damper
1=Rot.exchanger
2=Plate exchanger
3=Liquid exchanger
4=Not connected
VentSettings.Cor_NightC
oolDayLimit
R
40479
22
Settings, Free cooling
If outdoor temp. has been higher during
daytime, free cooling is activated at
night
VentSettings.Cor_NightC
oolHighLimit
R
40480
18
Settings, Free cooling
If outdoor temp. is higher at night, free
cooling is stopped
VentSettings.Cor_NightC
oolLowLimit
R
40481
10
Settings, Free cooling
If outdoor temp is lower at night, free
cooling is stopped
VentSettings.Cor_NightC
oolRoomLimit
R
40482
18
Settings, Free cooling
If room temp is lower at night, free
cooling is stopped
VentSettings.Cor_NightC
oolStartTime
X
40483
0
Settings, Free cooling
Start time free cool function
VentSettings.Cor_NightC
oolStopTime
X
40484
7
Settings, Free cooling
Stop time free cool function
VentSettings.Cor_NightC
oolHeatBlockTime
I
40485
60
Settings, Free cooling
Time in minutes to block heat output
when starting after running free cooling