Chapter 1 Corrigo with EXOline, Modbus and BACnet communication 7
BACnet MS/TP Configuration
Upon delivery, the BACnet MS/TP protocol is disabled as a default. To enable BACnet
communication, the function must first be activated. The default communication settings upon
delivery are as follows:
Speed = 9600 bps
MAC address = 0
Device ID = 2640
Max Master = 127
Function port1
Slave
BACnet MS/TP
communication
port1
Active
Device name
CorrigoVentilation
MAC
0
Device ID low
2640
Device ID high
0 (x10000)
Speed
9600 bps
Max master address
127
Device name
This is the name of the device, as shown on the BAS when discovering devices.
MAC
The MAC address of the device. This needs to be unique only to the subnet to which the device is
attached.
Device ID
The ID of a device, used to identify it on the BACnet network. This number cannot be duplicated
anywhere on the BACnet network and must therefore be unique. To set an ID value of 34600, the
low number would be set to 4600 and the high number to 3.
Speed
Sets the communication speed of the MS/TP network. This value is typically set to 38400 or 76800
but can be 9600, 19200, 38400 or 76800.
Alarm delays in BACnet
The alarms for an object have only one common delay time, even if the object includes three different
alarms. The long delay time is displayed in the used BACnet tool.
Max master address
The max master is the MAC address of the highest master device on the BACnet MS/TP network
segment. Setting this number above the highest MAC address will decrease network performance.
For additional information, see the Corrigo PICS document, available via www.regincontrols.com.