Manual Corrigo Ventilation, revision R Chapter 17 Configuration 105
The remaining 2°C are the neutral zone between cooling and exchanger and between exchanger and
heating.
Split settings
exchanger
0% at HCOut= 32%
100% at HCOut= 50%
Split settings
heating
0% at HCOut= 54%
100% at HCOut= 100%
Split settings
cooling
0% at HCOut= 30%
100% at HCOut= 0%
Split settings
extra Sequence Y4
0% at HCOut= 0%
100% at HCOut= 0%
Split settings
extra Sequence Y5
0% at HCOut= 0%
100% at HCOut= 0%
17.30.7 Outdoor temp. for control mode change
If the unit is configured for combined Supply air/Room control this menu permits the setting of the
change-over outdoor temperature.
Outdoor temp for
control mode change
13.0°C
54%
50%
32%
30%
0%
0%
Controller
signal
Cooling
HeatingHeat
exch.
Output signal
100%
100%
Heat demand