16
3.3 Conguring the Software for EL Pre-Heater
After all the physical installations for pre-heating are complete the unit software needs to be setup using the
control panel.
Follow procedure below.
1 Access rights
Go to Access Rights by using the UP/DOWN
arrow buttons. Select by pressing the RIGHT arrow
button.
Temperature
Air Control
Time settings
→Access Rights
2 Log on
Choose Log on. Select by pressing the RIGHT
arrow button.
→Log on
Log off
Change password
3 Password
Enter password 1111 by pressing OK followed by
the UP/DOWN arrow buttons. Select next digit by
pressing the RIGHT arrow button. Press OK when
all 4 digits have been entered.
Go back 2 steps using the LEFT arrow button.
Log on
Enter password xxxx
Actual level: None
4 Conguration menu
Go to Conguration by using the UP/DOWN
arrow buttons. Select by pressing the RIGHT arrow
button.
Man/auto
Settings
Conguration
Access Rights
3
Use the control panel to program the unit for electric
pre-heating. See chapter 3.3 on how to do software
conguration.