401131 Commissioning Record

Compact Air Handling Units
Commissioning Record
Systemair Inc.
6
1.3 Alarm conīšæguration
Alarm settings Def. setting Set value Alarm settings Def. setting Set value
1. Run Error Supply Air Fan
Class
Delay
The unit stopped at alarm
A
300 s
No
35. Ventilation manual mode
Class
Delay
The unit stopped at alarm
C
0 s
No
2. Run Error Extract Air Fan
Class
Delay
The unit stopped at alarm
A
300 s
No
36. Manual supply air control
Class
Delay
The unit stopped at alarm
C
0 s
No
3. Run Error, P1-Heater
(HW-units)
Class
Delay
The unit stopped at alarm
B
5 s
No
37. Manual Supply Air Fan mode
Class
Delay
The unit stopped at alarm
C
0 s
No
4. Run error, P1-Cooler
(Cold water pump)
Class
Delay
The unit stopped at alarm
B
5 s
No
38. Manual Supply Air Fan freq
control
Class
Delay
The unit stopped at alarm
C
0 s
No
6. Filter guard
Class
Delay
The unit stopped at alarm
B
300 s
No
39. Manual Extract Air Fan Mode
Class
Delay
The unit stopped at alarm
C
0 s
No
7. Flow guard
Class
Delay
The unit stopped at alarm
B
5 s
No
40. Manual Extract Air Fan freq
control
Class
Delay
The unit stopped at alarm
C
0 s
No
8. External frost guard
Class
Delay
The unit stopped at alarm
A
0 s
No
41. Manual heater control
Class
Delay
The unit stopped at alarm
C
0 s
No
10. Fire alarm
Class
Delay
The unit stopped at alarm
A
0 s
No
42. Manual exchanger control
Class
Delay
The unit stopped at alarm
C
0 s
No
11. External switch
Class
Delay
The unit stopped at alarm
C
0 s
No
43. Manual cooler control
Class
Delay
The unit stopped at alarm
C
0 s
No
12. External alarm
Class
Delay
The unit stopped at alarm
B
0 s
No
44. Manual P1-Heater
(HW-units)
Class
Delay
The unit stopped at alarm
C
0 s
No