415005 Topvex TR Operation and Maintenance Instructions
Topvex TR800, TR1300, TR1800, TR4000 Operation and Maintenance Instructions
Systemair Inc.
15
Main menu item Sub-menu item 1 Sub-menu item 2 Explanations
Outdoor
comp.Setp. 1
-4°C = 5.9 CFM
32°C = 0 CFM
Act. Comp: 0
CFM
Set the SAF airow
compensation for the settable
outdoor temperature. The
outdoor compensation is linear
and is set using two parameter
pairs which give the value of the
compensation at two different
outdoor temperatures. The
compensation can be positive or
negative.
Shows the actual airow
compensation.
Flow control
EAF
Actual: + INF
CFM
Setp.: CFM
Shows airow for the extract air
fan (constant airow control)
Only visible if the unit is
congured for Flow control
Flow control
EAF
Setp 1/1: 647.4
CFM
Setp 1/2: 323.7
CFM↓
Set the normal (1/1) and
reduced (1/2) airow for the
extract air fan
Outdoor
comp.Setp. 1
-4°F = 5.9 CFM
32°F = 0 CFM
Act. Comp: 0
CFM
Set the EAF airow
compensation for the settable
outdoor temperature. The
outdoor compensation is linear
and is set using two parameter
pairs which give the value of the
compensation at two different
outdoor temperatures. The
compensation can be positive or
negative.
Shows The actual airow
compensation.
Pressure
control SAF
Actual: in.wg
Setp.: in.wg
Shows the actual external
pressure and set point for the
supply air fan.
Only visible if the unit is
congured for “Pressure
control” (VAV)
Pressure
control SAF
Setp 1/1: 0.6
in.wg
Setp 1/2: 0.4
in.wg
Set the external pressure set
point for normal speed (1/1)
and reduced speed (1/2) for the
supply fan.