CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 4 Input Register 27
Signal name
EXOL type
Modbus address
Default value
Function
Description
InputOutput.Exp2AnaOut4
R
30246
Analogue
outputs
Value of AO4 Exp. Unit 2
InputOutput.Exp2AnaOut5
R
30247
Analogue
outputs
Value of AO5 Exp. Unit 2
VentSettings.Cor_ExpAo(0)
X
30248
Analogue
outputs
Connected signal on AO1 Exp. Unit
1:
0=Not used
1=Y1-Heating
2=Y2-Exchanger
3=Y3-Cooling
4=SAF
5=EAF
6=Y6-Humidity
7=Split of Y1, Y2 or Y3
8=Extra unit
9=Heat/Cool (change over)
10=Extra sequence Y4
VentSettings.Cor_ExpAo(1)
X
30249
Analogue
outputs
Connected signal on AO2 Exp. Unit
1:
(See signal list for AO1)
VentSettings.Cor_ExpAo(2)
X
30250
Analogue
outputs
Connected signal on AO3 Exp. Unit
1:
(See signal list for AO1)
VentSettings.Cor_ExpAo(3)
X
30251
Analogue
outputs
Connected signal on AO4 Exp. Unit
1:
(See signal list for AO1)
VentSettings.Cor_ExpAo(4)
X
30252
Analogue
outputs
Connected signal on AO5 Exp. Unit
1:
(See signal list for AO1)
VentSettings.Cor_ExpAo(5)
X
30253
Analogue
outputs
Connected signal on AO1 Exp. Unit
2:
(See signal list for AO1)
VentSettings.Cor_ExpAo(6)
X
30254
Analogue
outputs
Connected signal on AO2 Exp. Unit
2:
(See signal list for AO1)
VentSettings.Cor_ExpAo(7)
X
30255
Analogue
outputs
Connected signal on AO3 Exp. Unit
2:
(See signal list for AO1)
VentSettings.Cor_ExpAo(8)
X
30256
Analogue
outputs
Connected signal on AO4 Exp. Unit
2:
(See signal list for AO1)
VentSettings.Cor_ExpAo(9)
X
30257
Analogue
outputs
Connected signal on AO5 Exp. Unit
2:
(See signal list for AO1)