The variables presented in the display of the Corrigo are:
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh).
Lenze
No settings necessary.
Lenze frequency converters are controlled via Modbus. Communication, alarms and certain
indications can be read.
The following signals can be read/written from/to the frequency converter:
Address
Modbus register
Name
Scaling
Type
49
32049, 42049
Password
-
-
50
32050, 42050
Parameter version
-
-
45
30045, 40045
FB Speed reference (SP)
50
%
2
30002, 40002
FB Status word
-
Binary
512
32512, 42512
Acc. Motor output
1
kW
528
32528, 42528
Motor frequency
10
Hz
509
32509, 42509
Current
1
A
511
32511, 42511
Output
1000
kW
506
31506, 41506
DC voltage
1
V
30
32110, 42110
Active error
-
Error code
27
32027, 42027
FB Status word
-
Binary
The variables presented in the display of the Corrigo are:
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh).
Omron V1000
Connected via RS485:
R+ is connected to S+
R- is connected to S-
R+/S+ is connected to B on port 1 or 2
R-/S- is connected to A on port 1 or 2
Parameters
The following parameters must be set from the display of the frequency converter:
H5-01 (0x425): Slave address, set to = 1 for Supply air fan and = 2 for Exhaust air fan
H5-07 (0x42B): RTS Control, set to = 1 (enabled) for activation of RS485
o1-03 (0x502): Frequency reference units, set to = 1 for 0-100%.
H5-03 (0x427): Parity, set to = 0 (no parity)
Default values should be used for remaining parameters. The following values may not be changed:
H5-02 (0x426): Communication speed, default =3 (9600)
H5-04 (0x428): Stopping method after communication error, default = 3 (no stop)
H5-11 (0x43C): Communication Enter Function, default=1 (Enter command not
necessary)
H5-12 (0x43D): Run command, default=0 (bit 0=forward start/stop, bit 1= reverse