Corrigo ventilation 3.4 manu

64 Chapter 10 Temperature Manual Corrigo Ventilation, revision R
Support control heating
Support heating
Room temp for
Start: 15.0°C
Stop: 21.0°C
Support control cooling
Support cooling
Room temp for
Start: 30.0°C
Stop: 28.0°C
Frost protection temperature
Frost protection
Actual: 30.9°C
Deicing exchanger
Deicing exchanger
Actual: 11.2°C
Setp: -3.0°C
Hysteresis: 1.0°C
Heat exchanger efficiency monitoring
Efficiency exch
Actual: 93%
Output exchanger
Actual: 100%
Recirculation (see 5.1.11)
Temp.setpoint when
recirc. (Supply/
Extract/Room)
18.0°C
Offset SAF when
frequency control
and recirculation
0.0 Pa
"Offset SAF" makes it possible to add an offset to the setpoint during normal operation. If pressure
control has been configured, the offset is set in Pascal (Pa) or in inch of water gauge (in.wg). When
in.wg is selected, a factor (x100) is used both in the program and in the displays. If flow control has
been configured, it is set in m
3
/h. If manual control has been configured, the offset is set in percent.
Extra unit (see 5.2)
Extra unit
Actual: 21.2°C
Setp: 20.0°C
Enthalpy control
Enthalpy indoors
33.8 kJ/Kg
Enthalpy outdoors
35.0 kJ/Kg