CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

50 Chapter 5 Holding Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
TimePro.TimeGroupStatu
sFanFullSpeed
X
40393
4
Manual/Auto
Manual/Auto Full Speed time channel:
Modbus:
0=Manual-Off
1=Manual-On
2=Forced Off
3=Forced On
4=Auto
BACnet:
1=Manual-Off
2=Manual-On
3=Forced Off
4=Forced On
5=Auto
TimePro.TimeGroupStatu
sFanHalfSpeed
X
40394
4
Manual/Auto
Manual/Auto Half Speed time channel:
Modbus:
0=Manual-Off
1=Manual-On
2=Forced Off
3=Forced On
4=Auto
BACnet:
1=Manual-Off
2=Manual-On
3=Forced Off
4=Forced On
5=Auto
TimePro.TimeGroupStatu
sCor_ExtraTimeGroup1
X
40395
4
Manual/Auto
Manual/Auto Timer output 1:
0=Manual-Off
1=Manual-On
2=Forced Off
3=Forced On
4=Auto
TimePro.TimeGroupStatu
sCor_ExtraTimeGroup2
X
40396
4
Manual/Auto
Manual/Auto Timer output 2:
0=Manual-Off
1=Manual-On
2=Forced Off
3=Forced On
4=Auto
TimePro.TimeGroupStatu
sCor_ExtraTimeGroup3
X
40397
4
Manual/Auto
Manual/Auto Timer output 3:
0=Manual-Off
1=Manual-On
2=Forced Off
3=Forced On
4=Auto
TimePro.TimeGroupStatu
sCor_ExtraTimeGroup4
X
40398
4
Manual/Auto
Manual/Auto Timer output 4:
0=Manual-Off
1=Manual-On
2=Forced Off
3=Forced On
4=Auto