CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 5 Holding Register 53
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_ExtraU
nitSetP
R
40435
18°C
Extra Unit
Setpoint Extra Unit
VentSettings.Cor_ExtraU
nitPID1Mode
X
40436
0
Extra Unit
Control mode Extra Unit
0=Heating Controller
1=Cooling Controller
VentSettings.Cor_ExtraU
nitPID1_Select(0)
X
40437
2
Manual/Auto
Manual/Auto Extra Unit Controller
0=Off
1=Manual
2=Auto
VentSettings.Cor_ExtraU
nitPID1_ManSet(0)
R
40438
0
Manual/Auto
Extra Unit Controller output if manual
mode
VentSettings.Cor_Recycl
eSetP
R
40439
18°C
Recirculation
Recirculation setpoint
VentSettings.Cor_Recycl
eMaxRoomTemp
R
40440
25°C
Recirculation
If higher room temp when
Recirculation run recirculation damper
is closed and fresh air damper is
opened
VentSettings.Cor_Recycl
eSAFOffset
R
40441
0
Recirculation
Setpoint offset if pressure/flow
controlled SAF (Pa)
VentSettings.Cor_Recycl
eEAFOffset
R
40442
0
Recirculation
Setpoint offset if pressure/flow
controlled EAF (this is not used)
VentSettings.Cor_SAFAi
rFlowK
R
40443
100
SAF/EAF Pressure
and Flow
K-constant for counting air flow SAF
airflow = Cor_AirFlowK *
Cor_SAFPressure^Cor_AirFlowx
VentSettings.Cor_SAFAi
rFlowx
R
40444
0.5
SAF/EAF Pressure
and Flow
X-constant for counting air flow SAF
VentSettings.Cor_EAFAi
rFlowK
R
40445
100
SAF/EAF Pressure
and Flow
K-constant for counting air flow EAF
airflow = Cor_AirFlowK *
Cor_SAFPressure^Cor_AirFlowx
VentSettings.Cor_EAFAi
rFlowx
R
40446
0.5
SAF/EAF Pressure
and Flow
X-constant for counting air flow EAF
VentSettings.Cor_EAFFr
equencyFact
R
40447
1
SAF/EAF Pressure
and Flow
Factor for controlling EAF if CAV fan
control is configured (EAF is
controlled by SAF with this factor)
VentSettings.Cor_ExtraS
eqCoilAutoMode
X
40448
2
Manual/Auto
Manual/Auto Extra Sequence Y4
0=Off
1=Manual
2=Auto
VentSettings.Cor_ExtraS
eqCoilManual
R
40449
0
Manual/Auto
Extra Sequence Y4 output if manual
mode
VentSettings.Cor_FilterA
larmTime
I
40450
0
Settings, Alarm
Delays
Time in month between filter exchange
(Service Alarm)