CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 5 Holding Register 55
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_Deman
dCO2Value2
R
40466
1000
CO
2
Activation of demand-controlled
ventilation, 1/1-speed
VentSettings.Cor_Deman
dCO2Diff
R
40467
160
CO
2
Hysteresis for stop of demand
controlled ventilation (ppm)
VentSettings.Cor_Cascad
eTemp
R
40468
13
Supply, Extract and
Room temperatures
Outdoor temp for switching between
outdoor compensated or cascade
control if Cor_VentControl = 4 or 5 (if
higher outdoor temp then cascade
control)
VentSettings.Cor_ExtraS
eqY5AutoMode
X
40469
2
Manual/Auto
Run mode Extra seq coil Y5 (0=Off,
1=Manual, 2=Auto)
VentSettings.Cor_ExtraS
eqY5Manual
R
40470
0
Manual/Auto
Manual setting Extra seq coil Y5
if manual mode
VentSettings.Cor_ExtraS
eqY5Min
R
40471
0
Actual/Setpoint
Min. limit for Y5 in Auto mode
VentSettings.Cor_Reduce
dSetPOffset
R
40472
0
Actual/Setpoint
Temperature setpoint offset in reduced
speed
VentSettings.Cor_Change
OverSelect
X
40473
2
Settings, General
Select change-over external:
Modbus:
0=Heating
1=Cooling
2=Auto
BACnet:
1=Heating
2=Cooling
3=Auto
VentSettings.Cor_VentC
ontrol
X
40474
0
Settings, General
Select temperature control mode:
0=Const. supply air
1=Outdoor compensated supply air
2=Cascade room temp control
3=Extract temp control
4=Outdoor dependent supply or room
temp
5=Outdoor dependent supply or extract
temp
6=Cascade outdoor compensated room
temp control
7=Cascade outdoor compensated
extract temp control