CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

74 Chapter 7 Frequency converters
Omron frequency converters are controlled via Modbus. Communication, alarms and certain
indications can be read.
The following signals can be read/written from/to the frequency converter:
Address
Modbus register
Name
Scaling
Type
3
30003, 40003
FB Speed reference (SP)
10
%
2
30002, 40002
Password
-
-
36
30036, 40036
Motor frequency
100
Hz
63
30063, 40063
Motor speed
1
+/- Rpm
39
30039, 40039
Current
10
A
40
30040, 40040
Output
10
kW
38
30038, 40038
DC voltage
10
V
33
30033, 40033
Status change
-
Binary
34
30034, 40034
Alarm
-
Binary
93
30093, 40093
Acc. Motor output
1
kW
The variables presented in the display of the Corrigo are:
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh).
Emerson Commander
Connections RS485-RJ45:
RJ45:2 (orange) is connected to B on port 1 or 2
RJ45:7 (white/brown) is connected to A on port 1 or 2
Possible termination resistor is connected between RJ45:1 (white/orange) and RJ45:8 (brown).
If Modbus communication is not initialised after powering up, disconnect the termination resistor and
try again.
Terminals
Connect terminal B4 (Drive enabled) to B2 (+24V)
Connect terminal B5 (Forward) to B2 (+24V)
Parameters
The following parameters must be set from the display of the frequency converter:
44: Slave address, set to = 1 (default) for Supply air fan and = 2 for Exhaust air fan
43: Baud rate: 9.6 (default: 19.2)
Default values should be used for remaining parameters.
Changing parameters
Deactivate the unit. The display should read “iH 0.0”. This is performed by
opening terminal B4.
Set parameter 10 to ”L3”, i.e. all parameters up to and including 95 can then be altered.
Set parameter 43 to 9.6 (9600 baud).