Set parameter 43 to 9.6 (9600 baud).
Emerson frequency converters are controlled via Modbus. Communication, alarms and certain
indications can be read.
The following signals can be read/written from/to the frequency converter:
Address
Modbus register
Name
Scaling
Type
114
30114, 40114
Speed selection
-
-
18
30018, 40018
FB Speed reference (SP)
10
%
1038
31038, 41038
FB Status word
-
-
615
30615, 40615
Control switch
-
Binary
501
30501, 40501
Motor frequency
10
Hz
2
30002, 40002
Max speed
10
Hz
504
30504, 40504
Motor speed
1
+/- Rpm
402
30402, 40402
Current
10
A
503
30503, 40503
Output
10
kW
505
30505, 40505
DC voltage
1
V
1040
31040 41040
Status change
-
Binary
The variables presented in the display of the Corrigo are:
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh).
LS
LS frequency converters are controlled via Modbus. Communication, alarms and certain indications
can be read.
LS iG5A
The following signals can be read/written from/to the frequency converter:
Address
Modbus register
Name
Scaling
Type
5
30005,40005
FB Speed reference (SP)
10
%
6
30006,40006
FB Status word
-
Binary
10
30010,40010
Motor frequency
100
Hz
31
30031,40031
Torque
100
%
21
30029,40029
RPM
1
Rpm
9
30009,40009
Motor current
10
A
13
30013,40013
Output
10
kW
12
30012,40012
Voltage
10
V
14
30014,40014
Status change
-
Binary
15
30015,40015
Alarm
-
Binary
29
30029,40029
Alarm 2
-
Binary
The variables presented in the display of the Corrigo are:
Frequency (Hz), Current (A), Output (kW), Accumulated power (kWh).
LS iS7
The following signals can be read/written from/to the frequency converter: