2.3 Technical data
Protection class .................................................................................................................. IP20
Display........................................................ 4 rows of 20 characters. Background illumination.
LEDs
Yellow ....................................................................................................... Settable parameter
Red ............................................................................................................... Alarm indication
Clock .................................................................. Year base 24 hour clock with battery backup.
Automatic summer-/winter-time changeover.
Operating system .......................................................................................................... EXOreal
Supply voltage .................................................... 24 V AC ±15%, 50…60 Hz or 21…36 V DC
Power consumption ........................................ 5 VA, 3 W (DC), model …W: 9 VA, 5 W (DC)
Dimensions .................................................................... 148x123x60 (WxHxD incl. terminals)
Casing .......................................................................... Standard Euronorm (8.5 modules wide)
Mounting ................................................................................................................ On DIN-rail
Operation
Climatic conditions according to IEC 721-3-3 ........................................................ Class 3k5
Ambient temperature ..................................................................................................0...50°C
Ambient humidity .............................................................................................. Max 95% RH
Mechanical requirements according to IEC721-3-3 .............................................. Class 3M3
Vibration .......................................................... IEC60068-2-6, Test FC, vibration Sinusoidal
Shock ................................................................................................ IEC60068-2-27, Test Ea
Transport
Climatic conditions according to IEC 721-3-2 ........................................................ Class 2k3
Ambient temperature .............................................................................................. -20...70°C
Ambient humidity .............................................................................................. Max 95% RH
Mechanical requirements according to IEC721-3-2 .............................................. Class 2M2
Vibration .......................................................... IEC60068-2-6, Test FC, vibration Sinusoidal
Shock ................................................................................................ IEC60068-2-27, Test Ea
Free fall .............................................................................................IEC60068-2-27, Test Ed
Storage
Climatic conditions according to IEC 721-3-1 ........................................................ Class 1k3
Ambient temperature .............................................................................................. -20...70°C
Ambient humidity .............................................................................................. Max 95% RH
Battery
Type .................................................................................... Replaceable Lithium cell, CR2032
Battery life ................................................................................................... Better than 5 years
Warning .................................................................................................... Low battery warning
Battery backup ............................................................................... Memory and real time clock
Communication
EXOline Port 1, insulated via a built-in RS485 contact.
EXOline Port 2, via a built-in RS485 contact.
EXOline TCP/IP.
Modbus communication via serial RS485 communication or TCP/IP.
BACnet/IP or BACnet MS/TP via RS485 (a BACnet router is needed).
LON serial communication.
Suitable model should be selected for appropriate needs.
EMC emission and immunity standard
This product conforms to the requirements of the EMC Directive 2004/108/EC through product
standards EN 61000-6-1 and EN 61000-6-3.
RoHS
This product conforms to the Directive 2011/65/EU of the European Parliament and of the Council.