415005 Topvex TR Operation and Maintenance Instructions

Topvex TR800, TR1300, TR1800, TR4000
Operation and Maintenance Instructions
Systemair Inc.
30
5.4.1 Alarms
The alarm button (pos.1, gure 6) opens the alarm queue. When pressing this button active and
non-acknowledged alarms will be displayed in the menu window. The alarm-LED (pos. 2, gure 6) will ash
if there are non-acknowledged alarms and be on (but not ashing) if the alarms are still active but have
been acknowledged. If there are multiple alarms, use UP/DOWN to move between them. An alarm can be
acknowledged or blocked by using OK and UP/DOWN. To abort and go back to start menu press cancel
and then press LEFT.
See Commissioning record for an overview of possible alarms.
5.4 Troubleshooting
Should problems occur, please check or correct the following before contacting your service representative.
Always check if there are any alarms active in the control panel. See section 4.3 to learn how to navigate
through the control panel menu. For more information on the alarm designations go to the Systemair
website (www.systemair.com/na/North-America/) and download the controller user manual.
1. Fan(s) do not start
Check if there are any alarm messages
Check if the automatic fuse AS1 is tripped (gure 3, pos. 8; gure 4-5, pos. 7)
Check if fan(s) thermal contact is tripped due to overheating (shows as “Fan alarm” in the control
panel).
Check the run status and the setting in control panel (schedules, auto/manual operation, airow set
points, etc.)
2. Wheel motor does not start
Check if there are any alarm messages
Check if the automatic fuse AS1 is tripped (gure 3, pos. 8; gure 4-5, pos. 7)
Check if the fuses in the fuse holders F1 & F2 are blown (gure 3, pos. 13; gure 4, pos. 8)
Check the run status and the setting in control panel (schedule, auto/manual operation, free cooling
active, etc.)
3. Reduced Airow
Check if there are any alarm messages
Check the run status and the setting in control panel (schedules, auto/manual operation, airow set
points, etc.)
Check if outdoor/exhaust air damper (if used) are opened
Check if lters need to be changed
Check if diffuser/louvers are opened
Check if diffusers/louvers need cleaning
Check if fans and/or exchanger need to be cleaned
Check for obstruction at the air inlets/outlets
Check ducts for visible damage and/or buildup of dust and debris
4. Cold supply air
Check if there are any alarm messages
Check the supply air temperature set point on the control panel
If electric re-heater is equipped, check if the automatic fuse AS2 is tripped (gure 3, pos. 9)
If electric re-heater is equipped, check if the overheating thermostat is tripped. If so, see section 2.2.6
If hydronic re-heater is equipped, check if the valve(s)/actuator(s) controlling the water ow are
functioning properly
Check if lters need to be changed
5. Noise/vibrations
Check if the unit is completely leveled
Check if fans and/or exchanger need to be cleaned
Check if the screws holding the fans are tightened properly