Corrigo ventilation 3.4 manu

Manual Corrigo Ventilation, revision R Chapter 17 Configuration 83
Chapter 17 Configuration
Start by logging on as Admin. See chapter 8.
Move the marker using the DOWN and UP buttons until it is opposite the menu ā€Configurationā€
and press RIGHT.
The configuration main menu is shown (different menus are visible depending on the configured
inputs and outputs).
Inputs/Outputs
Sensor settings
Control function
Fan control
Extra control unit
Extra sequence Y4
Extra sequence Y5
Heating
Exchanger
Cooling
Pump control
Free cooling
Support control
CO2/VOC control
Fire function
Humidity control
Exchanger de-icing
Cooling recovery
Enthalpy control
Min lim. dampers
External setpoint
Run ind/Motor prot.
Actuator type
Actuator run time
Actuat. period time
Step controllers
Recirculation
Pretreatment
Alarm settings
Communication
Other parameters
System
17.1 Inputs and outputs
AI
DI
UI
AO
DO
General
Free configuration
Any control signal can be bound to any in- and output, the only restriction being that digital signals
cannot be bound to analogue inputs and vice versa. It is up to the user doing the binding to make
sure that activated functions are bound to appropriate in- and outputs.
Delivery setting
On delivery, all physical in- and outputs have already been bound to a signal.
The delivery settings are suggestions only and can easily be changed.