88 Chapter 17 Configuration Manual Corrigo Ventilation, revision R
17.6 Extra sequence Y4
"Extra sequence Y4" can be configured to one of the following alternatives: "Active", "Active with
cooling recovery", "Active with enthalpy control" and "Active with both cooling recovery and
enthalpy control".
Mode Extra
sequence Y4
Not active
17.7 Extra sequence Y5
"Extra sequence Y5" can be configured to “Active” or “Not active”.
Mode Extra
Sequence Y5
Not active
17.8 Heating coil
Heating
Water
The heater can be set to "Water", "Electric", "Water/Electric" or "Not used".
For detailed description of heater alternatives, see section 5.1.2 Heater types.
17.9 Exchanger
Exchanger
Rot exchanger
The heat exchanger unit can be set to one of the following alternatives:
Plate exchanger
Rotating exchanger
Liquid connected exchanger
Mixing dampers
Not connected
Damper limiting for minimum outdoor air percentage is settable 0…100%.
In the submenu parameters for outdoor temperature control of exchanger can be set.
Outd temp control
of exch: Off
Outd temp start: 10°C
Diff stop: 0.2°C
For detailed description of exchanger alternatives, see section 5.1.3 Heat exchanger.