CORRIGO VENTILATION 3.X USER GUIDE
Table Of Contents
- About this user guide
- About Corrigo
- Display, buttons and LEDs
- The menu system
- Navigating the menus
- Running mode
- Temperature
- Setpoint Supply air temperature control
- Setpoint Outdoor temperature compensated Supply air control
- Setpoint Cascaded room temperature control
- Setpoint Cascaded extract air temperature control
- Setpoint Outdoor compensated room temperature/extract air control
- Support control heating/Support control cooling
- Frost protection temperature
- Exchanger de-icing
- Heat exchanger efficiency monitoring
- Recirculation
- Extra controller unit
- Enthalpy control
- Air control
- Pressure control SAF (there are also corresponding menus for EAF)
- Flow control SAF (there are also corresponding menus for EAF)
- Manual frequency control SAF (there are also corresponding menus for EAF)
- Frequency control external
- Frequency control SAF with EAF slave/flow control (also available for opposite function)
- CO2
- Humidity control
- Time settings
- Access rights
- Other functions
- Index
The menu system Corrigo ventilation user guide, revision F
18
Frequency control SAF with EAF slave/flow control (also available for
opposite function)
A pressure control where either the SAF or EAF is
operated as a slave. This function is also available
featuring flow control.
Controller output
comp if cooling
0 at R U S= 0 %
100 at R U S= 0 %
Controller output
comp if heating
0 at R U S= 0 %
100 at R U S= 0 %
Controller output
compensation
Not active
Compensation only
when
1/1-speed : No
defrosting: No
Pressure ctrl SAF
Actual: 480 Pa
Setp.: 490 Pa
Pressure ctrl SAF
Setp 1/1: 500 Pa
Setp 1/2: 250 Pa
Outdoor comp output
-20 °C = 0 Pa
10 °C = 0 Pa
Act comp: 0 Pa
Comp sens:Roomtp.1 15
°C = 0 Pa
20 °C = 0 Pa
25 °C = 0 Pa