2.3 Transport and Storage
The Topvex TR800-4000 should be stored and transported in such a way that it is protected against
physical damage that can harm panels, handles, display etc. It should be covered so that dust, rain and
snow cannot enter and damage the unit and its components. The appliance is delivered in one piece
containing all necessary components, wrapped in plastic on a pallet for easy transportation.
When transporting the Topvex TR800-4000 units use a forklift to transport the unit as shown below.
(Figure 5).
Warning
The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
Fig. 5 Transporting the unit
1 Warnings
The following admonitions will be presented in the different sections of the document.
Danger
Make sure that the Mains supply to the unit is disconnected before performing any maintenance or
electrical work!
All electrical connections must be carried out in accordance with local rules and regulations.
Warning
In order for the unit to be considered safely installed the doors if equipped with handles have to be
locked with a key to prevent unauthorized or accidental opening
The unit must be duct connected or in some other way provided with protection so that it is not
possible to come in contact with the fans through the duct connections
The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
used. Use protective clothing.
Caution
If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
Duct connections/duct ends should be covered during storage and installation
Do not connect tumble dryers to the ventilation system
Take care not to damage the water battery when connecting water pipes to connectors. Use a
spanner to tighten the connection.
Topvex FR03, FR06, FR08, and FR11
Installation instructions
206638
1
Systemair AB
Model TR4000-208-3 TR4000HW-208-3
Voltage CA 208 208
Frequency Hz 60 60
Phase 3 3
Current A 15.4 15.4
MCA A 17.3 17.3
MOP A 25 25
Total Fan Power W 4800 4800
EL Preheater Power kW N/A N/A
EL Reheater Power kW N/A N/A
MCA (w/ EL Preheat) A N/A N/A
MOP (w/ EL Preheat) A N/A N/A
HW Preheater Capacity BTU 92800 92800
HW Reheater Capacity BTU 101300 101300