Corrigo ventilation 3.4 manu

110 Chapter 18 Other functions Manual Corrigo Ventilation, revision R
18.4 Language
When the start menu is displayed, pressing the RIGHT button three times will display a menu in
which the language can be changed.
The different language files are stored in the application memory and are downloaded to the work
memory. If a Corrigo via E tool
©
has been reloaded with a newer program revision than the factory
revision, the controller will not allow language files to be downloaded from the application
memory. This is because there is a risk that the language files are not compatible with the new
revision. Therefore, you are limited to the two languages you have downloaded using E tool
©
.
18.5 Indication LEDs
Status indication can be found in the upper left corner of the master controller. For controllers with
display, the alarm indication and change mode LEDs are located in the keypad area.
Status indication
Designation
Colour
Description
Tx
Green
Port 1, Transmitting
Rx
Green
Port 1, Receiving
Serv (…LON models)
Yellow
Service LED LON, commissioning
LAN (…W models)
Yellow/Green
Green: Connected to other network
equipment
Blinking green: Network traffic
Blinking yellow: For identifying
P/B (Power/Battery)
Green/Red
Power on/Battery error
Controllers with built-in display
Red
Alarm indication
Yellow
Change mode
18.6 Changing the battery
This procedure requires knowledge of proper ESD protection; i.e. an earthed wristband must be
used!
When the alarm ”Internal Battery” is activated and the battery LED lights up red, the battery for
backup of program memory and real-time clock has become too weak. The battery is replaced as
described below. A backup capacitor saves the memory and keeps the clock running for at least 10
minutes after the power supply is removed. Therefore, if the battery replacement takes less than 10
minutes, there will be no need to reload the program, and the clock will continue to run normally.
The replacement battery must be of the type CR2032.